background image

IMTP 2.2 - ITTP 2.2/4/5.5/7.5 

    

ENG

 

 

5.2  Pump hydraulic connection 

Connect the hydraulics according to the regulations in force. 
This product can work when connected to the waterworks or taking water from a water cistern. 
If  you  connect  the  system  to  the  waterworks,  you  have  to  respect  the  regulations  in  force  issued  by  local 
authority (Common, local authority, etcÉ). It is important to put a pressure switch on the inlet leader; it switches 
off the motor power in case of low pressure (it is a dry-working external protection).  The inverter have two ports 
for a normally-closed generic contact: EN and C on the logic board (fig. 4). 
Verify the amount of pressure between the waterworks and the maximum pump pressure, does not exceed the 
maximum pump pressure value (nominal pressure) 
Besides, it is important to put a pressure gauge on the outlet leader, so it is possible to regulate the pressure 
factory setting value, according to the real conditions of the system. 

On the outlet leader it is necessary to install 

a pressure gauge with an output signal between 0 – 5 Vdc or 4 – 20 mA; this signal is an input to the inverter.

 

As a rule it would be better to install flexible or rigid pipes on inlet and outlet branches, on-off valves on inlet and 
outlet branches, a no return valve, a membrane surge tank. To avoid drying the system for replacement of the 
membrane surge tank, pressure gauge or pressure transducer, it would be better to install some on-off valves 
between the tank connection and the system. Put the pressure transducer downstream the non-return valve, if it 
is present. It would be better to install a cock, used during the system calibration; it is not necessary if there is 
an exit near the pump.  Be sure the surge tank allows the system pressure. 
Check the pre-stress pressure of the surge tank before connecting it to the system. 

 
 

5.3  Electric connections 

Check voltage and frequency of the power supply are the same of the nominal values of the control system, that 
are written on the box. Be certain of having a good short-circuit protection in your electric system. 
Before working, be certain all the circuit is without voltage (also the connections voltage clear). Disconnect the 
inverter from the power supply before working on electrical or mechanical parts of the system. 

Wait at least 2 minutes after the power supply disconnection before working on the inverter; this 
allow  the  capacitors  discharge  (in  order  to  be  sure  they  are  completely  discharged,  the  led 
placed inside the inverter, on the electronic board, have to be completely switched off).  
 
If the local regulation about electric system provides for a magneto-thermal differential switch, 

install one. Select the protection with curve for alternative current or pulsing current (type A or C).  
The unit is equipped with all those technical arrangements required to ensure a good  functioning under normal 
situations installation. 
The  control  system  has  a  entry-filter  and  it  conforms  to  the  EMC  directive,  also  have  a  current  overload 
protection which guarantees absolute protection when the Inverter is combined with motors that not exceed

 

the 

maximum power.

 

IMPORTANT:  For  EMC  is  necessary  that  the  power  wires  of  control  panel  and  motor  power  wires  (when  the 
motor are separated from the inverter) are shielded type (or armoured) with individual conductors of appropriate 
section  (current  density  <=  5  A/mm2).  These  cables  must  be  the  minimum  length  necessary.  The  screen 
conductor must be connected to the ground by both sides. On motor use the metal case for connection to the 
ground of the screen. 
To  avoid  loops  that  can  create  mass  disturbances  radiated  (antenna  effect),  the  motor  operated  by  the 
frequency  converter  must  be  connected  on  the  ground  individually,  always  with  a  low-impedance  using  the 
metallic box of the machine. 
The wires from power supply to frequency converter and wires from frequency converter Ð motor (if the motor is 
separated to the Inverter) must be spaced as much as possible, not to create loops, not make them run parallel 
less than 50 cm. 

 
 

5.4   Motor-pumps phases connection 

 

The  single-phase  inverter 

IMTP2.2

  must  be 

installed  on  asynchronous  three-phase  motor 
with  100-240Vac  50/60  Hz  voltage  supply. 
Phases  must  be  configured  to  Delta  mode  if 
the  motor  is  230V    /  400V    (most  common 
case, as in Figure 3). 

 

 

Figure 3 – Delta motor phases connection 

 

 

Summary of Contents for IMTP 2.2 M-RS

Page 1: ...Motor Pump Inverter Type IMTP 2 2 M RS ITTP 2 2 M RS ITTP 4 M W RS ITTP 5 5 M W RS ITTP 7 5 W RS ENG Operation and maintenance handbook...

Page 2: ...5 Electric connection to Line and Motor 7 5 6 Pressure transducer connection on different types 8 5 7 Connections on the electronic board 9 6 STARTING AND PROGRAMMING 12 6 1 First Inverter Using Self...

Page 3: ...0mA or 0 5V output The control logic works with an output of 5 or 15V switchable that supplies the pressure transducer MINIMUM FLOW WORKING PROTECTION to prevent a closed delivery working the control...

Page 4: ...ty regulations could endangers others and damage the devices which can lead to loss of warranty The results of the non observance of the security rules can be Malfunctioning of the system Danger to ot...

Page 5: ...to remove the paint from the contact surface It is necessary to avoid ground loop that is like an antenna for EMC emission Power supply must be admitted on working condition don t lift or carry the m...

Page 6: ...ic system Before working be certain all the circuit is without voltage also the connections voltage clear Disconnect the inverter from the power supply before working on electrical or mechanical parts...

Page 7: ...wo cables connectors from the logic board J1 26 poles e J2 4 poles for IMTP2 2 ITTP2 2 Figure 5 or J5 26 poles for ITTP4 7 5 Figure 8 Connect the 3 motor terminals U V W on the power board on IMTP2 2...

Page 8: ...nnectors for IMTP ITTP2 2 fig 5 and J9 for ITTP4 7 5 fig 8 if previously disconnected making sure they are firmly fixed don t forget the clamp on J9 for ITTP4 7 5 fig 8 Replace and close the box using...

Page 9: ...9 IMTP 2 2 ITTP 2 2 4 5 5 7 5 ENG 5 7 Connections on the electronic board Figure 5 Logic board of IMTP2 2 ITTP 2 2...

Page 10: ...10 IMTP 2 2 ITTP 2 2 4 5 5 7 5 ENG Figure 6 Power board of IMTP 2 2 Figure 7 Power board of ITTP 2 2...

Page 11: ...11 IMTP 2 2 ITTP 2 2 4 5 5 7 5 ENG Figure 8 Logic board of ITTP 4 7 5 Figure 9 Power board of ITTP 4 7 5...

Page 12: ...pump is fully of water and close completely the outlet of the pump Pressing START for the Self Regulation Check for the registration of the curve of the pump for the regulation of the stop for closed...

Page 13: ...after the variation press ENTER Decrease the reference pressure during functioning ESC To exit to the function and automatically saving START Pump start STOP Pump stop If pressed with the key during...

Page 14: ...iangle see 5 3 Set the rotation direction 0 1 Default 0 Regulation of the minimum flow power for the motor stop in closed output condition Regulation of the dry working power stop default 80 Pump data...

Page 15: ...flow stop Default 12 second 15 second for ITTP4 7 5 4 Re start delay time after minimum flow stop Default 1 second 5 Dry working stop delay time for pump filling Default 40 seconds 6 When cos go down...

Page 16: ...faulty current control Automatic re start final stop after 10 consecutive events 13 Input Voltage under limit Input voltage under the minimum working limit Automatic re start final stop after 10 cons...

Page 17: ...output power to the motor then stop the motor and the inverter show Over Temperature IGBT alarm Inverter Temperature alarm Temperature of the electronic board of the inverter is too high and the inve...

Page 18: ...at pump haven t any defect fault seal impellers etc that can cause a big power absorbing also without water in dry condition 13 A group of two or more inverters cannot communicate between each other i...

Page 19: ...ctives and to national law following the technical standards Machines 98 37 CE Low Voltage 73 23 CE e successive modifiche and subsequent amendments IEC EN 61000 6 1 CEI EN 61000 6 4 ETSI EN 301 489 1...

Page 20: ...na Ind Esmoriz Sector C 8 36 13 86 O GPS OLIJU Manufacturing 40 57 27 11 N PORTUGAL PORTUGAL 4520 475 Rio Me o Zona Industrial de Rio Me o Avenida Santiago N 43 40 57 37 20 N 8 35 50 10 O GPS OLIJU Co...

Reviews: