background image

50

immediately, before leaving the site remember to:
-

seal the ends of the piping,

-

Ask the person in charge of the site to make sure that
the piping does not get squashed, bent or damaged
in any way.

g) The piping and the appliances (internal and external

units) are connected by means of binders. After the
piping has been cut and the nut which is found on the
connection has been inserted onto the piping (fig. 15),
the piping must be binded in accordance with the norms.

h) In order to tighten each joint it is necessary to:

-

grease the thread with refrigeration oil (do not use
other types of oil),

-

close the joint initially by hand,

-

tighten the joint with a dynamometrically calibrated
spanner with the following torque values:

-

14“ 18 Nx m (1,4“ 1,8 kgxm) for line attachments from
6,4“ 6 mm.

-

33“ 40 Nx m (3,3“ 4,0 kgxm) for line attachments from
9,5“ 10 mm.

-

50“ 60 Nx m (5,0“ 6,0 kgxm) for line attachments from
12,7“ 12 mm.

IMPORTANT: To avoid deforming the internal unitis
attachments when tightening, hold the welded part of the
joint with a spanner and tighten the other part with the
dynamometric spanner.

i ) Once the attachments have been tightened, the lineis

seal must be tested. In order to test the seal a cylinder
of anhydrous nitrogen is connected to the external unitis
gas pipe service connection (fig. 16) (after having
unscrewed the cap) (it is connected to the service
connections in the case of the Multisplit external units)
by means of a flexible with a 1/4" attachment and a
pressure reducer.

Open the cylinder and the pressure reducer until the
pressure in the circuit reaches 3 bars and then close the
cylinder. If the pressure does not descend after 3 minutes,
this means that there are no major leaks and the pressure
can be raised to 15 bars. After the cylinder is closed, the
pressure must remain constant for another 3 minutes. In
any case, to be completely sure it is advisable to apply
a solution of soap suds and check that bubbles do not
formed in the solution.  If the pressure descends and the
solution test gives no results, insert some R410A into the
circuit and identify the leakage by means of a leak finder.
Since there should be no weldings in the system,  the
leaks are nearly always found around the joints. Elimina-
te all gas leaks by tightening or repairing the joints and
repeat the seal test. Once the operation has been
concluded, reassemble the caps, checking carefully that
they have been closed properly.

IMPORTANT: In the case of Multisplit this operation must
be carried out on all the connections one after the other. The
search for gas leaks must be carried out each time on the
circuit which depends on the connection in question.

j)

Once the seal test has been passed, every trace of air,
nitrogen and humidity must be completely extracted
from the circuit. Lower the pressure within the circuit by
means of a vacuum pump until the pressure reaches an
absolute value equal to 50 Pa and, leaving the pump

Fig. 15

Fig. 16

1 CUT THE PIPE WITH A

WHEEL TYPE PIPE CUTTER

PERPENDICULAR CUT

2 DEBURR

PREVENT
CHIPS FALLING
INSIDE THE
PIPE

4 THE END OF THE PIPE MUST

PROTRUDE BY 0.5 mm

3 INSERT THE NUT IN THE

PIPE

6 THE FLARE MUST BE

CIRCULAR

SERVICE FITTING AND
PIPE FITTING

TAP MECHANISM

SERVICE FITTING

Summary of Contents for ClimaPiu 8 HE HP

Page 1: ...MANUALE D INSTALLAZIONE MANUALE D USO MANUAL FOR INSTALLATION INSTRUCTIONS FOR USE...

Page 2: ...37 Manual for Installation...

Page 3: ...nclusion 57 USE 1 Presentation 59 2 Precautions 59 2 1 Nomenclature of parts 60 3 Display console 60 3 1 Air deflector 60 4 Use of appliance by remote control 61 4 1 Appliance activation disactivation...

Page 4: ...icult nor dangerous Duringinstallationandmaintenanceallprecautionsspecified in this handbook and on the labels inside each appliance must be observed as should normal common sense and also the securit...

Page 5: ...verify yield EN 814 2 High load test conditions EN 814 ClimaPi 8 HE HP ClimaPi 12 HE HP ClimaPi 15 HE HP KW 2 20 3 38 4 05 KW 2 31 3 54 4 25 W 670 1 120 1 440 W 660 1 098 1 411 A cold hot 3 0 2 9 5 2...

Page 6: ...rnal units for cooling only and with heat pump for systems from the Split series 2 1 2 External units for cooling only and with heat pump for systems from the Split series MAIN ON OFF SWITCH 2 1 Overa...

Page 7: ...barriers with in 2 m from the outlet of the appliance could result in air bypasses and a consequent reduction in the applianceis output fig 1 fig 1 bis Condensate drainage is facilitated The emission...

Page 8: ...xed to the wall in the selected location by means of the four blocks and screws supplied Other types of screws and blocks may also be used 8 mm as long as they have a raised head If the wall onto whic...

Page 9: ...le must be drilled for this also in the position indicated in the instructions supplied with the accessory and assemble it in accordance with these instructions b Insert the condensate removal line co...

Page 10: ...necting terninal board fig 8 in accordance with the modes indicated in the electric circuit arrangement see paragraph 3 7 g Place a stopper between the appliance and the wall fig 9 to create sufficien...

Page 11: ...irculation and maintenance as specified in the overall dimensions Pathways are not obstructed The appliance can be securely fixed to the base Neither fumes nor noise emissions can disturb the neighbou...

Page 12: ...ectedlocationshencethereshould be no danger of dirt accumulation under the appliance On a rigid metal base Brackets metal support sections etc In this case the appliance must always be fixed to the ba...

Page 13: ...locks if necessary b Tighten the anchor bolts slightly c Check that the appliance is horizontal in both directions fig 12 If necessary shim the supports until the appliance is level d Tighten the anch...

Page 14: ...e lines connecting up all the internal parts of the Multisplit must not be more than 15 m in each direction in any case for more than 10 m it is necessary to top up the charge with 20 g of R410A for e...

Page 15: ...er and the pressure reducer until the pressure in the circuit reaches 3 bars and then close the cylinder Ifthepressuredoesnotdescendafter3minutes thismeansthattherearenomajorleaksandthepressure can be...

Page 16: ...iffusion of the cooler within the appliance 3 6 Laying and connection of condensate removal lines 3 6 1 For models 12 15 The appliance features an automatic system that automatically drains any conden...

Page 17: ...tioned atmosphere The seal trap must on no account have a 1 5 m difference in height less than the applianceis lower wire fig 18 If on the contrary the condensate drainage line flows into a receptacle...

Page 18: ...and they must have a minimum diameter of 11 5 mm Model Conductor section mm2 Earth Input phase and neutral ClimaPi 8 HE 2 5 3 ClimaPi 12 HE 2 5 3 ClimaPi 15 HE 2 5 3 The power supply cable and earth w...

Page 19: ...ance being left off immediately after installation is completed To carry out this operation it is necessary to unscrew the cap on the service valve which can be found on the external unitis gas line c...

Page 20: ...he refrigerant is in its liquid state Once charged wait for at least 10 before starting the compressor to allow the fluid to evaporate e When the operation is finished remove the flexible from the ser...

Page 21: ...s without any warning When an alarm is triggered the LEDs flash The dirty filter alarm does not shut the appliance down and the LED does not flash IMPORTANT If the appliance does not function as descr...

Page 22: ...ce with the instructions given in the Technical Handbook If the charge is proven scarse still following the instructios given in the Technical Handbook a Identify and eliminate the leakage b Reset the...

Page 23: ...58 Instruction for Use...

Page 24: ...Handbook supplied with the appliance 2 Themainsvoltagemustremainwithinthelimitsspecified in the paragraph Operational limits For safety reasons the appliance must be connected up to a fully reliable...

Page 25: ...ng C5 Red LED indicator signalling the need to clean the filters and operation inhibition of the multisplit hp C6 Remote control signal receiver 3 Display console 1 Emergency micro pushswitch only use...

Page 26: ...eries are inserted by opening the little snap door at the back of the remote control and are positioned according to the polarity signs at the back of the opening fig 2 Once the batteries have been in...

Page 27: ...ing on this switch the appliance will automatically run to obtain optimum comfort conditions in the air conditioned environment The system temperature and the fan speed are adjusted automatically acco...

Page 28: ...m shows up on the display symbolized by a fan At this stage it is possible to select the fan speed desired see chapter 5 8 Fig 8 4 6 Heating function heat pump models only This mode is employed for he...

Page 29: ...sition block the mobile deflector in the desired position by pressing the T9 switch while the deflector is still moving By pressing the T9 switch once more the deflector resumes automatic movement IMP...

Page 30: ...dels only reduction in the appliance s noise level energy saving advantages In order to activate the night function press the T3 switch after selecting the functioning mode T4 and the desired temperat...

Page 31: ...m setting until PROGR 1 ON shows up on the display Activation time Program No 1 b Using the T7 switch set the controls to the time at which you want to activate the appliance with the 1st program Ever...

Page 32: ...integrity Fig 18 4 14 Use of appliance without remote control If the remote control gets damaged its batteries are dead or it gets broken the appliance may be controlled in the Automatic mode only by...

Page 33: ...ed with a timed pilot light red LED which indicates the necessity to clean the filter which 320 hours after the last resetting was done it will light up reminding you to check the condition of the fil...

Page 34: ...ng of each season by means of a vacuum cleaner onto which a soft brush has been applied As regards the heat pump models the external unit s battery shouldbecleanedatleasttwiceayear bothatthebeginning...

Page 35: ...such a situation is evident from the fact that the green LED on the console does not light up in such a case check to see if there is voltage in the mains for example by switching on a lamp in the ho...

Page 36: ...71...

Page 37: ...72 COD 272891A Edizione 03D Via Guido Rossa 1 3 42044 Gualtieri Reggio Emilia Italy Tel 39052222601 Fax 390522828745 service olimpiasplendid it...

Reviews: