53
3.7.1 Power supply link up
The power must be supplied to the appliance by means of
a general disconnector equipped with delayed fuses or with
a thermomagnetic automatic circuit breaker with the following
current capacities:
Model
Capacity
ClimaPiù 8 HE
: 10 A
ClimaPiù 12 HE
: 10 A
ClimaPiù 15HE
: 10 A
For security reasons the general disconnector should be
near the feeder and should also be in a clearly visible
location.
The supply cordons must be provided with copper conductors
with the following unitary sections (the under indicated
values refer to a maximum lenght of the lines fo 15 meters).
Besides the cordons must be of the type H07-RR-F and they
must have a minimum diameter of 11,5 mm.
Model
Conductor section mm
2
Earth
Input
(phase and neutral)
ClimaPiù 8 HE:
2,5
3
ClimaPiù 12 HE:
2,5
3
ClimaPiù 15 HE:
2,5
3
The power supply cable and earth wire must be connected
to the power supply terminal board on the indoor unit as
indicated in Fig. 20 featuring three terminals: one for the
phase, one for neutral and a third for the earth connection.
3.7.2 Connecting the connection cable
(see also the diagrams inside the side of the sheet in
front of the electric panel)
A connection must be set up between the two units so that
the outdoor unit features the same controls as the indoor
unit.
All these connections must be carried out with copper wires
which connect the applianceis connection terminals
according to the diagram in fig. 21 (Split), 22 (Split with heat
pump).
Fig. 20
Fig. 21