background image

PROCOOL 16 E

ENGLISH

EN - 9

 

27. LEAK DETECTION METhODS

 

The  following  leak  detection  methods  are  deemed  acceptable  for  systems 

containing flammable refrigerants.

 

Electronic leak detectors shall be used to detect flammable refrigerants, but 

the sensitivity may not be adequate, or may need re-calibration. (Detection 

equipment shall be calibrated in a refrigerant-free area). 

 

Ensure that the detector is not a potential source of ignition and is suitable for 

the refrigerant used

 

Leak  detection  equipment  shall  be  set  at  a  percentage  of  the  LFL  of  the 

refrigerant  and  shall  be  calibrated  to  the  refrigerant  employed  and  the 

appropriate percentage of gas (25 % maximum) is confirmed. 

 

Leak detection fluids are suitable for use with most refrigerants but the use of 

detergents containing chlorine shall be avoided as the chlorine may react with 

the refrigerant and corrode the copper pipe-work. 

 

If a leak is suspected, all naked flames shall be removed/ extinguished. 

 

If a leakage of refrigerant is found which requires brazing, all of the refrigerant 

shall be recovered from the system, or isolated (by means of shut off valves) 

in a part of the system remote from the leak. 

 

Oxygen free nitrogen (OFn) shall then be purged through the system both 

before and during the brazing process.

 

28. REmOVaL anD EVaCuaTIOn

 

When breaking into the refrigerant circuit to make repairs or for any other 

purpose conventional procedures shall be used.

 

However, it is important that best practice is followed since flammability is a 

consideration. 

 

The following procedure shall be adhered to:

•  Remove refrigerant;

•  Purge the circuit with inert gas;

•  Evacuate;

•  Purge again with inert gas;

•  Open the circuit by cutting or brazing.

 

The refrigerant charge shall be recovered into the correct recovery cylinders. 

The system shall be flushed with OFn to render the unit safe. 

 

This process may need to be repeated several times. 

 

Compressed air or oxygen shall not be used for this task.

 

Flushing shall be achieved by breaking the vacuum in the system with OFn 

and continuing to fill until the working pressure is achieved, then venting to 

atmosphere, and finally pulling down to a vacuum. 

 

This process shall be repeated until no refrigerant is within the system. When 

the final OFn charge is used, the system shall be vented down to atmospheric 

pressure to enable work to take place. 

 

This operation is absolutely vital if brazing operations on the pipe-work are to 

take place.

 

Ensure that the outlet for the vacuum pump is not close to any ignition sources 

and there is ventilation available.

Summary of Contents for PROCOOL 16 E

Page 1: ...EN INSTRUCTION FOR USE AND MAINTENANCE PROCOOL 16 E Caution risk of fire...

Page 2: ......

Page 3: ...qualified service agent 11 Servicing shall only be performed as recommended by the equipment manufacturer or qualified service agent 12 All working procedure that affects safety means shall only be c...

Page 4: ...3 b Replacement of batteries 16 3 3 PROTECTION FUNCTION 16 3 3 a Frost Protection Function 16 3 3 b Overflow Protection Function 16 3 3 c Automatic Defrosting 16 3 3 d Compressor Protection Function 1...

Page 5: ...eSERVICEdepartmentinthecompany CUSTOMER TECHNICAL SERVICE Index Paragraphs marked with this symbol contain very important information and recommendations particularly as regards safety Failure to comp...

Page 6: ...llation please ensure that the portable air conditioner is properly grounded If you have any questions please contact the manufacturer 1 Place the appliance in a flat and dry place and keep a distance...

Page 7: ...ioner and avoid spilling water or other liquids into the unit warning low burning velocity mateial 12 Do not use insecticide sprays or other flammable substances near the portable air conditioner 13 D...

Page 8: ...ts may not contain an odour 8 R32 is a refrigerant gas in compliance with the european directives on environment do not pierce any part of the refrigerant circuit 9 Do not use means to accelerate the...

Page 9: ...lowing precautions shall be complied with prior to conducting work on the system b Work procedure Work shall be undertaken under a controlled procedure so as to minimise the risk of a flammable gas or...

Page 10: ...all be applied to installations using flammable refrigerants The charge size is in accordance with the room size within which the refrigerant containing parts are installed The ventilation machinery a...

Page 11: ...tions The use of silicon sealant may inhibit the effectiveness of some types of leak detection equipment Intrinsically safe components do not have to be isolated prior to working on them 24 Repair to...

Page 12: ...ree nitrogen OFN shall then be purged through the system both before and during the brazing process 28 Removal and evacuation When breaking into the refrigerant circuit to make repairs or for any othe...

Page 13: ...to re use of reclaimed refrigerant It is essential that electrical power is available before the task is commenced a Become familiar with the equipment and its operation b Isolate system electrically...

Page 14: ...ing order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of flammable refrigerants In addition a set of calibrated weighing scales shall be...

Page 15: ...onal wheel 1 ENGLISH EN 12 1 FEATURES AND COMPONENTS Fig 1 Brand new appearance compact structure smooth line simple and generous shape Functions cooling dehumidification fan and drainage User friendl...

Page 16: ...the package will not cause a leak of the refrigerant charge The maximum number of pieces of equipment permitted to be stored together will be determined by local regulations 2 2 INSTALLATION AND ADJU...

Page 17: ...ow sealing plate assembly The flat end of the exhaust pipe joints must be snapped into place The pipe cannot be distorted nor has substantial turning greater than 45 Ensure the exhaust pipe is kept cl...

Page 18: ...ing or set up the timer to the required timer setting This function is not available under FAN mode and DEHUMIDIFYING mode Display WINDOWS DOWN Button While in timer mode press this button to adjust t...

Page 19: ...s 3 3 PROTECTION FUNCTION 3 3 a Frost Protection Function This portable air conditioner has a built in protection mode The unit will enter this mode if the exhaust pipe temperature drops below a certa...

Page 20: ...such as benzene alcohol gasoline etc otherwise the surface of the air conditioning will be damaged 4 1 b Clean the filter screen If the filter becomes clogged the portable air conditioner will lose i...

Page 21: ...r will automatically flow into the water con tainer To ensure items don t get misplaced keep the drainage cover and water plug in a safe place while draining During drainage the body can be tilted sli...

Page 22: ...place so it does not get damaged between uses e Cover the main unit with a plastic bag Put the air conditioning in a dry place keep it out of the reach of children and take dust control measures f Rem...

Page 23: ...een The air inlet or outlet is blocked Clear obstructions The unit is noisy The unit is sitting on an uneven surface Ensure the portable air conditioner is sitting on a flat hard surface Compressor do...

Page 24: ...d or replaced if the goods fail to be of acceptable quality and the failure does not amount to a major failure If you have any queries regarding your product or its warranty please find contacts below...

Reviews: