ALARM CODES 

 

 

Display 
Indication 

Likely Cause 

Suggested Solution 

Relative humidity drops below very low values (<22%). 

Activate the dehumidifier with 
higher ambient 
humidity conditions. 

"Hr" flashing 

Humidity sensor broken. 

Change humidity sensor or 
whole PCB (according to the 
model). 

"tE" flashing 

The ambient evaporator temperature sensor 
is damaged. 

Change ambient temperature 
sensor or whole PCB (according 
to the model). 

"Lo" flashing 

The ambient temperature is too low. It means that 

after 30 

minutes of operation in defrosting mode (compressor 
stopped and fan working) the defrosting temperature does 
not exceed St. Alarm reset automatically after room temp 
rise up St.

 

Activate the dehumidifier with 
higher ambient humidity 
conditions. 

"EE" flashing 

The EEPROM of the PCB is damaged. 

Change the PCB (for some 
model models only). 

 

Mnemonic 

Range scheduled 

Parameters set 

Description 

Co 

20 min 

50 min 

20 

Compressor in defrosting ON time 

Cf 

3 min 

15 min 

Compressor minimum OFF time 

Ft 

-9°C 

+9°C 

Frost accumulation temperature 

St 

0°C 

+9°C 

End of defrosting temperature 

 

• AUTOTEST MODE 

 

By pressing the keys 4+5 for 3 seconds in sequence with the unit in Stand-by, the following 
sequence is started (each phase has a duration of  3 seconds): 

switch-on of all symbols of the displays 

display of the software release 

activation of the fan (max speed managed according to the model, resistor powered when provided) and 

compressor, displaying the code At on digits to the right side and the evaporator probe temperature 
to the left side. 
The compressor remains ON continuously, independently of the set point and the tank level switch; the 
pause between stop and subsequent start and the defrosting function are also excluded. 
The tank level symbol is active if the tank is absent (switch open), off if the tank is present (input closed). 
Pressing the key 5 the software refresh the standard display mode as room air temperature and relative humidity values. 
Press the stand-by key or disconnect the power supply to quit the auto test mode.

 