14
Installing the stove
The floor on which the stove is installed must be even and
horizontal. The stove may only be installed on an adequate
load-bearing floor. The stove can be stood on a metal floor
sheet or glass sheet to protect the flooring.
If the flooring or carpet is inflammable, a stable and non-
combustible spark protection plate must be used. This
must extend 50 cm to the front and 30 cm to each side
beyond the edge of the combustion chamber opening.
Under the stove no spark protection plate is required.
Assembly sequence
●
If intended, install the OEC.
●
Install the side cladding.
For the stove according to EN 13229, only the original
Olsberg cladding kit is to be used.
●
The Ø150mm stovepipe connection can be installed at
the top or rear. The stove is supplied ready for connec-
tion from above. If you wish to connect it at the rear, the
following steps must be carried out to make the neces-
sary modifications:
- Remove cover from back panel. Cut out thermal insu-
lation in the area of the stovepipe.
- Replace the connector sleeve and the sealing cover.
●
Decide where the stove is to be installed. There must be
no objects made of combustible materials within a dis-
tance of 80 cm of the stove’s radiation area, measured
from the combustion chamber’s inspection glass, nor
may any be placed within this area subsequently.
Depending on the installation position of the stove in
front of walls that need to be protected (flammable or
load-bearing), the following distances from walls need
to be observed in accordance with the position of the
combustion chamber door to the wall / side panel or
the back panel (see schematic diagram).
When not dealing with walls that need to be protect-
ed, you merely need to observe a minimum distance of
approx. 5 cm to allow for proper heat dissipation.
●
Install the pipe lining (provided on site) in the chimney.
The connection height can be individually specified for
a top stovepipe connection, however should not exceed
1.5 m from the connector sleeve. For the rear stovepipe
connection heights please refer the “Technical Data“
chapter. No combustible material is permitted within a
radius of 20 cm around the stove pipe.
●
Connect the stovepipe at both connection points with
stove putty so that the stove pipe is permanently sealed.
●
Push the stove onto its planned position and orient it so
that the stovepipe fits into the pipe lining.
The stovepipe connections must be tight. The stove-
pipe must not protrude into the chimney.
Bear in mind that on partition walls in accordance with
test specification EN 13240 the temperature of 85°C
can be reached, and with light wallpaper or similar
combustible construction materials this can result in
colour changes.
15
87°
80
15
2,5
Dimensions in cm