15
A
A
Installing the stove
The floor on which the stove is installed must be
even and horizontal. The stove may only be in-
stalled on an adequate load-bearing floor. The
stove can be stood on a metal floor sheet or glass
sheet to protect the flooring.
If the flooring or carpet is inflammable, a stable
and non-combustible spark protection plate must
be used. This must extend 50 cm to the front and
30 cm to each side beyond the edge of the com-
bustion chamber opening. Under the stove no
spark protection plate is required.
Asembly sequence
●
If intended, install the OEC.
●
The Ø150mm stovepipe connection can be in-
stalled at the top or rear. The stove is supplied
ready for connec- tion from above. If you wish to
connect it at the rear, the following steps must be
carried out to make the necessary modifications:
‐
Break out the cover in the back panel.
‐
Replace the connector sleeve and the sealing
cover.
●
Decide where the stove is to be installed. There
must be no objects made of combustible materials
within a dis- tance of 80 cm of the stove
‟
s radiation
area, measured from the combustion chamber
‟
s in-
spection glass, nor may any be placed within this
area subsequently.
Depending on the installation position of the
stove in front of walls that need to be protected
(flammable or load-bearing), the following dis-
tances from walls need to be observed in ac-
cordance with the position of the combustion
chamber door to the wall / side panel or the back
panel (see schematic diagram).
When not dealing with walls that need to be protect-
ed, you merely need to observe a minimum dis-
tance of approx. 5 cm to allow for proper heat dissi-
pation.
If the stove is set up with the turntable, then the
turnta- ble must be positioned in such a manner
that the radi- ation area of the glass pane cannot
be turned in the di- rection of components that
must be protected, or the distance must be at
least 80 cm.
●
Install the pipe lining (provided on site) in the
chimney. The connection height can be individu-
ally specified for a top stovepipe connection, how-
ever should not exceed
1.5 m from the connector sleeve. For the rear
stovepipe connection heights please refer the
“Technical Data“ chapter. No combustible material
is permitted within a radius of 20 cm around the
stove pipe.
●
Connect the stovepipe at both connection points
with stove putty so that the stove pipe is perma-
nently sealed.
●
Push the stove onto its planned position and orient
it so that the stovepipe fits into the pipe lining.
The stovepipe connections must be tight. The
stove- pipe must not protrude into the chim-
ney.
Stove installed straight in corner
Stove installed diagonally in corner
Bear in mind that on partition walls in accordance
with test specification EN 13240 the temperature
of 85°C can be reached, and with light wallpaper
or similar combustible construction materials
this can result in colour changes.
15
15