background image

15

 P/N 30149, Rev. G [12/15/2016]

A.2 Burner Electrodes

Adjustment of electrode tips with respect to each other, 

nozzle, burner head is very important to ensure smooth 

start-ups and to permit efficient combustion.

Beckett AF and AFII Burners

• Electrode gap: 5/32 inch.
• 

Distance above horizontal center-line: 5/16 inch. 

Older instruction sheets specify 7/16 inch. Current 

specification is 5/16 inch.

• Distance ahead of nozzle: 1/16 inch.
• “Z” dimension, distance from front of end cone 

(head) to face of nozzle should be 1-1/8 inches. If 

ceramic head is used, distance from end cone to 

nozzle face is increased to 1-3/8 inches.

Riello 40F, & BF Burners

• Electrode gap: 5/32 inch.
• 

Distance above horizontal center-line: 13/64 inch. 

• Distance ahead of nozzle: 5/64 to 7/64 inch.

A.3 Start Up

Use following instructions to set the burner:

1. 

Shut off electrical power to the furnace.

2. 

Install oil pressure gauge to pressure port on oil pump. 

(Refer to oil pump specification sheet included with 

burner instructions).

3. 

Restore electrical power to furnace.

4. 

Start furnace and bleed all air from fuel oil lines.

5. 

Close purge valve and fire the unit.

6. 

Allow furnace to warm up to normal operating 

temperatures. During this time, set pump pressure in 

accordance with data provided in Appendix A, Table A-1 

thru A-4.

7. 

Chimney vented units

 - Drill 1/4" test port in 

venting between furnace flue outlet and draft regulator 

(barometric damper) to take smoke readings.

8. 

Sidewall vented units

 - Do not drill. Use test port 

in the supplied appliance connector to take smoke 

readings.

9. 

When furnace has reached "

steady state

" (after ap

-

proximately 10 minutes). Set combustion air damper 

to get TRACE of smoke for chimney vented units and 

ZERO smoke for sidewall vented units.

10. 

Check system temperature rise. 

Temperature rise is the 

difference between return air temperature measured at 

a point near return air inlet, and supply air temperature 

measured near furnace outlet

System temperature rise is listed on furnace rating 

plate. If temperature rise is too high, airflow must 

be increased. If temperature rise is too low, slow fan 

down.

11. 

After air adjustments have been completed, recheck 

the over fire draft at test port on burner mounting plate 

shown in Figure 2. Over fire draft should be adjusted to 

-0.02 inches w.c. 

12. 

Turn burner off. Observe duct thermometer in supply 

air stream, note temperature blower fan stops. Fan 

adjustments can be made by moving dipswitch settings 

on timer control board for fan off delay. 

13. 

Check operation of limit switch. 

A.  Shut off power to furnace. 
B.  Temporarily remove neutral wire from PSC blower 

motor or remove 5 pin power connector from ECM 

blower motor. Isolate AC line voltage pins on 5 pin 

power connector with electrical tape to prevent 

electric shock hazard.

C.  Restore electrical power to furnace. 
D.  Set thermostat above room temperature. 
E.  After three or four minutes of burner operation, 

limit control should turn burner off. 

F.  When limit function test is complete, shut off 

electrical power to furnace, replace neutral wire to 

PSC blower motor or 5 pin power connector to ECM 

blower motor. Restore power. 

G.  Blower fan will start up immediately. Once 

temperature has dropped and limit control has 

reset, fan will operate until fan off time is reached. 

H.  Oil burner will resume operation and continue until 

thermostat is satisfied. 

I.  Restore thermostat setting to comfortable 

temperature.

14. 

Set heat anticipator adjustment in thermostat (if so 

equipped), by removing "R" or "W" wire to thermostat. 

Read amperage draw between the two wires. Failure 

to remove one of the wires from thermostat while 

performing this test could burn out heat anticipator. 

Set heat anticipator to amperage measured.

15. 

Run furnace through at least three full cycles before 

leaving the installation, to ensure all controls are 

operating properly.

16. 

Check all joints in any positive pressure venting system 

for leaks before leaving the installation site

A.4 Special Instructions For Units Equipped With 

Riello Burners

Riello specifications are listed in Tables A-1 and A-4. 

Consult Riello Installation Instructions supplied with Burner 

for specific information concerning burner adjustments, 

operation, and trouble-shooting.

APPENDIX A - CHECK OUT AND ADJUSTMENTS

Summary of Contents for BML-60B22

Page 1: ...BMLV Lowboy Model with ECM Series B Oil Fired Warm Air Furnaces INSTALLATION OPERATION MAINTENANCE MANUAL P N 30149 Rev G 12 15 2016 ECR International 2210 Dwyer Avenue Utica NY 13501 web site www ecr...

Page 2: ...anent Shipping Weight LB Width A Length B Height C Supply D x E Return F x G Diameter Height H BML BMLV 22 51 32 20 x 19 20 x 18 5 26 20 x 20 x1 240 LB 55 8 cm 130 8 cm 81 3 cm 52 cm x 49 cm 52 1 cm x...

Page 3: ...ation 8 15 Oil Filter 8 16 Oil Burner Nozzles 8 17 Oil Burner Adjustment 8 18 Burner Electrodes 8 19 Burner Primary Safety Control 9 20 Combustion Chamber 9 21a Circulating Air Blower BML BMLV 9 21b C...

Page 4: ...Canada HRAI or by other means prescribed or approved by the local authority having jurisdiction United States Manual J titled Load Calculation published by the Air Conditioning Contractors of America...

Page 5: ...ust have a control to prevent operation of either system unless dampers are in full heat or full cool position Air heated by the furnace shall not pass through evaporator coil unless coil is specifica...

Page 6: ...pipes sloping upward toward the chimney at a rate of one quarter inch per foot Flue pipe should not be smaller in cross sectional area than flue collar on the furnace Flue pipe should connect to chim...

Page 7: ...it control is thermally operated and automatically resets Limit control is factory installed pre set and is not adjustable If limit control opens with United Technologies 1158 120 BML electronic fan c...

Page 8: ...fficiency BML and BMLV operate most efficiently with No 1 smoke spot on Bacharach Scale Dust will eventually build up on air moving components of oil burner assembly resulting in decreased air supply...

Page 9: ...ch run and lack block ends on the trunk ducts These systems may require modification to provide some resistance to the airflow to prevent over amping of direct drive blower motor Selecting a lower blo...

Page 10: ...ow for 7 5 minutes After 7 5 minutes has elapsed motor will increase to 100 of rated airflow Used to provide dehumidification and improve system efficiency Continuous Fan Operation When thermostat con...

Page 11: ...aintenance Failure to do so could result in death or serious injury If cleaning is necessary shut off oil supply shut off power to the furnace and remove burner Use stiff brush with wire handle brush...

Page 12: ...lled in electrical power supply line to OFF 24 Operating Instructions BMLV Before Lighting 1 Open all supply and return air registers and grilles 2 Open all valves in oil pipes 3 Turn on electric powe...

Page 13: ...g 0 50 usgph F3 3 in BML 80B2 BMLV 80B2 76 000 AF76BNHS 0 65 80 A 100 psig 0 65 usgph F3 3 in BML 90B2 BMLV 90B2 85 000 AF76BNHS 0 75 80 A 100 psig 0 75 usgph F3 3 in 1 Head is shielded by ceramic ins...

Page 14: ...ieve zero smoke A 1 OIL BURNER AIR ADJUSTMENT Consult oil burner instructions provided in furnace documents envelope for specific information concerning burner adjustments operation and troubleshootin...

Page 15: ...h airflow must be increased If temperature rise is too low slow fan down 11 After air adjustments have been completed recheck the over fire draft at test port on burner mounting plate shown in Figure...

Page 16: ...obvious APPENDIX A CHECK OUT AND ADJUSTMENTS FIGURE 3 UNITED TECHNOLOGIES 1158 120 FAN TIMER BOARD BML FIGURE 4 UNITED TECHNOLOGIES 1168 1 ECM TAP BOARD BMLV Where oil shut off valve from oil storage...

Page 17: ...eed CFM External Static Pressure Inches w c 0 20 0 30 0 40 0 50 0 60 BML 60 90 100 10T DD 1 2 HP 7 1 70 F High 1722 1645 1561 1462 1375 Med High 1604 1545 1473 1383 1302 Med Low 1147 1133 1106 1063 10...

Page 18: ...ON ON D 1 5 SW3 ADJUST POS SW4 DELAY POS DIP Switch Position CFM DIP Switch Position INPUT 1 2 1 2 USGPH OFF OFF A 0 OFF OFF A 0 65 ON OFF B 15 ON OFF B 0 85 OFF ON C 15 OFF ON C 0 75 ON ON D N A ON...

Page 19: ...100 10T 3 x 2 T O 7 x 4L380 1 2 HP 3 x 7 x 4L380 1 2 HP 1 5 3 5 1 2 HP 600 1400 BML 90 100 10T 3 x 0 T O 7 x 4L380 1 2 HP 3 x 7 x 4L380 1 2 HP 1 5 3 5 1 2 HP 600 1400 Table A 11 Airflow Characteristi...

Page 20: ...20 P N 30149 Rev G 12 15 2016 APPENDIX B WIRING DIAGRAMS Chimney Vent Furnace Wiring Diagram BML BMLV...

Page 21: ...21 P N 30149 Rev G 12 15 2016 APPENDIX B WIRING DIAGRAMS Direct Vent Furnace Wiring Diagram BML BMLV...

Page 22: ...ts off burner Circulator fan is energized immediately at heat speed EFT opens the oil primary control T T connections Circulating fan runs as long as limit string stays open If there is a call for coo...

Page 23: ...ay burn out heat anticipator of standard 24 vac thermostat or cause harm to components within micro electronic thermostat Before checking oil primary control perform these preliminary checks repair or...

Page 24: ...pair light leak if necessary Open safety switch Check for open limit or auxiliary limit Check internal wiring connections loose connectors etc Furnace will not start without first pushing oil primary...

Page 25: ...l supplier Frozen oil line Gently warm oil line Insulate oil line Outdoor piping size may require increased diameter Oil burner sputtering at nozzle Electrodes out of adjustment or defective Check ele...

Page 26: ...e rise is too high speed up blower fan Defective high limit control Test high limit function of all limit switches Use duct thermometer to verify accuracy of limit control Check for obstructions to ai...

Page 27: ...12 15 2016 Model No Serial No Date Installed Contractor Contact Address Postal Code Telephone No After Hours No Fuel Supplier Fuel Oil Supplier Contact Telephone No After Hours No APPENDIX D HOMEOWNER...

Page 28: ...675 Sight Glass Cover Plate 29850 Sight Glass Gasket 2 per unit 29870 Sight Glass 29876 17 Flue Pipe Collar 27476 18 Air Filter 20 x 20 x 1 Permanent 2180032 19 Control Panel 30010 20 Control Panel Co...

Page 29: ...ng and Wheel 100 10T Belt Drive 30627 Blower Motor 1 2 HP One Speed 102000154 Motor Pulley 3 1 4 x 1 2 2240001 Blower Pulley 7 x 3 4 2240008 Belt 4L380 2240017 Blower Base 2 per unit 109005826 Grommet...

Page 30: ...er Motor 1 7 HP 3450 RPM PSC 28907 Beckett Clean cut Oil Pump A2EA6520 29688 Solid State Ignitor 28558 Oil Primary Combustion Control 7505P1530 Air Tube Combination FBX80HGXS 28561 Flame Retention Hea...

Page 31: ...31 P N 30149 Rev G 12 15 2016 Model BML and BMLV Diagram Direct Drive Model Shown 37...

Page 32: ...P N 30149 Rev G 12 15 2016 ECR International 2210 Dwyer Avenue Utica NY 13501 web site www ecrinternational com...

Reviews: