Instructions for Horizontal Right with Top Venting
1.
Remove 2.5” knockout and connect 2” nipple ap-
proximately 7” long (fi eld supplied) to the coupler on the
exhauster. Ensure exhauster coupler outlet is facing right
side approximately 15°.
6.
Remove two (2) 7/8” knockouts and install the conden-
sate trap bracket by removing and reusing the 2 top panel
screws, install condensate trap with gasket, hold in place
with 2 screws (all parts supplied in parts bag).
2.
Connect 2” elbow and 2” vent pipe (fi eld supplied).
7.
**IMPORTANT** Connect a 1/2” tee fi tting (fi eld sup-
plied) to the outlet of the condensate trap.
3.
Install gasket on panel then vent bracket, use three (3) self
tapping screws (all parts from parts bag). If using 1.5” or
3” vent, make transition as close as possible to the unit
and on a vertical section.
8.
Connect 1/2” drain tube (fi eld supplied) and route to fl oor
drain or condensate pump.
4.
Remove 2.5” knockout and connect 2” air intake coupler
with gasket on the outside of unit, use the 2” nut to fasten
this (all parts from parts bag). **Refer to page 26 for
inducer orientation**
9.
Connect one end of the 5/8” tubing (in parts bag) to the
drain on the front manifold cover, route to the larger
outlet on the condensate trap, cut excess tube and hold
in place with supplied hose clamps. Tubing should slope
towards drain trap with no sags.
5.
Connect 2” street elbow (from parts bag) and intake pipe
(fi eld supplied). If using 1.5” or 3” intake, make transition
as close as possible to the unit and on a vertical section.
10.
Connect one end of the 1/2” tubing (in parts bag) to the
lower drain outlet on the exhauster coupler, route to the
smaller inlet on the condensate trap, cut excess tube and
hold in place with supplied hose clamps. Tubing should
slope towards drain trap with no sags.
15 - VENT AND DRAINING OPTION - HORIZONTAL RIGHT
Instructions for Horizontal Right with Right Side Venting
1.
Connect two (2) 2” Street elbows (in parts bag) to the
coupler on the exhauster (Add 2” nipple for 120K BTU
units). Ensure exhauster coupler drain outlet is facing
downward 15°.
6.
Remove two (2) 7/8” knockouts and install the conden-
sate trap bracket by removing and reusing the 2 top panel
screws, install condensate trap with gasket, hold in place
with 2 screws (all parts supplied in parts bag).
2.
Remove 2.5” knockout and connect 2” vent pipe (fi eld
supplied). If using 1.5” or 3” vent, make transition as close
as possible to the unit and on a vertical section.
7.
**IMPORTANT** Connect a 1/2” tee fi tting (fi eld sup-
plied) to the outlet of the condensate trap.
3.
Install gasket on panel then vent bracket, use three (3) self
tapping screws (all parts from parts bag). If using 1.5” or
3” vent, make transition as close as possible to the unit
and on a vertical section.
8.
Connect 1/2” drain tube (fi eld supplied) and route to fl oor
drain or condensate pump.
4.
Remove 2.5” knockout and connect 2” air intake coupler
with gasket on the outside of unit, use the 2” nut to fasten
this (all parts from parts bag). **Refer to page 26 for
inducer orientation**
9.
Connect one end of the 5/8” tubing (in parts bag) to the
drain on the front manifold cover, route to the larger
outlet on the condensate trap, cut excess tube and hold
in place with supplied hose clamps. Tubing should slope
towards drain trap with no sags.
5.
Connect 2” street elbow (from parts bag) and intake pipe
(fi eld supplied). If using 1.5” or 3” intake, make transition
as close as possible to the unit and on a vertical section.
10.
Connect one end of the 1/2” tubing (in parts bag) to the
lower drain outlet on the exhauster coupling, route to the
smaller inlet on the condensate trap, cut excess tube and
hold in place with supplied hose clamps. Tubing should
slope towards drain trap with no sags.
Figure 22 -
Horizontal Right with Right Side Venting
Figure 23 -
Horizontal Right with Top Venting
31