4
2.0 PRODUCT INFORMATION
CLEARANCE (minimum) TO COMBUSTIBLES
Top of Supply Plenum
1” (25 mm)
Front (Maintenance)
36” (915 mm)
Rear
1”
(25
mm)
Side – Non-Access
1” (25 mm)
Side – Access maintenance
24” (610 mm)
Flue Pipe
9” (229 mm)
Floor (Can be installed directly on combustible or non-combustible)
DRAFT PRESSURE
Breech draft pressure
-0.01” WC minimum
BURNER TUBE INSERTION
HTL-100
6-3/8"
(162
mm)
HTL-200
9-1/2"
(240
mm)
AIR/BLOWER DATA
Maximum external static pressure
0.50” WC
Maximum cooling unit capacity
HTL-100, up to 3.0 tons.
HTL-200, up to 5.0 tons.
Maximum air temperature rise
85°F
MOTOR/BLOWER
HTL-100
1/2 hp 4 Speed PSC / G10-8 DD or 1/2 hp 5 speed ECM / G10-8 DD
HTL-200
3/4 hp 4 Speed PSC / GT12-10 DD or 3/4 hp ECM 5 speed / GT12-10 DD
FAN/HIGH LIMIT CONTROL
United Technologies 1158-120 Fan Center & Thermo-Disk (7” stem)
FLUE-PIPE CONNECTION
5” breech
CLEANOUTS
Front breech cover & burner opening (HTL)
THERMOSTAT
Any wall thermostat
Thermostat adjustment as per thermostat manufacturer installation.