background image

9

MAINTeNANce AND seRVIce

Routine Maintenance by home Owner

Other than remembering to arrange for the annual professional 

servicing of the furnace by the service or installation contractor, the 

most important routine service performed by the homeowner is to 

maintain the air filter or filters. A dirty filter can cause the furnace to 

over-heat, fail to maintain indoor temperature during cold weather, 

increase fuel consumption and cause component failure.
The furnace filter(s) should be inspected, cleaned or replaced month-

ly. The furnace is factory equipped with a semi-permanent type filter. 

If the filter is damaged, replace with filters of the same size and type. 

(See Parts Listing Ref. No. 21). 
During the routine service, inspect the general condition of the fur-

nace watching for signs of oil leaks in the vicinity of the oil burner, 

soot forming on any external part of the furnace, soot forming 

around the joints in the vent pipe, etc. If any of these conditions are 

present, please advise your service or installation contractor.

Annual service by contractor

!

  

CAUTION

THE COMBUSTION CHAMBER (FIREPOT) IS FRAG-

ILE. USE CARE WHEN INSPECTING AND CLEANING 

THIS AREA.

The heat exchanger should be inspected periodically and cleaned 

if necessary. If cleaning is necessary, SHUT OFF POWER TO THE 

FURNACE and remove the burner. Using a stiff brush with a wire 

handle, brush off scale and soot from inside the drum and flue pipe. 

To clean the radiator, remove the clean-out caps screws, and remove 

the caps carefully to avoid tearing the gaskets.  A wire brush can be 

used to loosen dirt and debris on the inside surfaces of the radiator. 

Clean out all accumulated dirt, soot and debris with a wire handled 

brush and an industrial vacuum cleaner. Before replacing the clean-

out caps, inspect the gaskets. If the gaskets are broken, remove the 

remnants and replace with new gaskets. 
The blower motor is factory oiled and permanently sealed.  DO NOT 

LUBRICATE. Excess oil causes premature electric motor failure.
Inspect the blower fan. Clean if necessary.
Oil Burner Maintenance: Follow the instructions of the oil burner 

manufacturer. (See oil burner manufacturer's instructions supplied 

with furnace or burner). It is advisable to change the oil burner 

nozzle and oil filter on an annual basis.
The venting system should be cleaned and inspected for signs of 

deterioration. Replace pitted or perforated vent pipe and fittings. The 

barometric damper should open and close freely.
All electrical connections should be checked to ensure tight con-

nections. Safety controls such as the high limit controls should be 

tested for functionality. The fan control should be checked to ensure 

that the fan on and off delay function continues to start and stop the 

blower fan at the optimal settings.

before lighting

Open all supply and return air registers and grilles.
Open all valves in oil pipes.
Turn on electric power supply.

To light unit

Set the thermostat above room temperature to call for heat. The 

burner should start. NOTE: It may be necessary to press the RESET 

button on the primary combustion control relay.
There will be a fan on time delay before the circulating fan is ener-

gized. The United Technologies 1158-120 has an adjustable fan on 

time that is set by selecting the dipswitch combination displayed in 

Table 2 

on page 6

.

 This fan on delay can be set at 30, 60, 90 or 120 

seconds. Set the thermostat below room temperature. The oil burner 

should stop.
The air circulation blower will continue to run until the time off 

setting selected on the electronic fan timer control times out.  The 

United Technologies 1158-120 has an adjustable fan off time of 1, 2, 

4,or 6 minutes.
The necessary adjustments to the fan control settings should be 

determined by measuring the temperature of the air in the supply 

air take-off, or within the first few inches of the supply air trunk. The 

OPeRATINg INsTRucTIONs (hTl-D)

side mid point of the transition is usually ideal, providing that the 

thermometer probe is beyond the "line of sight" wherein false read-

ings from radiant heat could be observed. System temperature rise is 

the difference in temperature between the supply air and return air.
To check the operation of the limit switch, shut off power to the 

furnace. Temporarily remove the neutral wire from the direct drive 

blower motor. Restore the electrical power to the furnace and set the 

thermostat above room temperature. 
After three or four minutes of burner operation, the limit control 

should turn the burner off. When the limit function test is complete, 

shut off electrical power to the furnace, replace the neutral wire to 

the blower fan motor, and then restore power. The blower fan will 

start up immediately. Once the temperature has dropped and the 

limit control has reset, the fan will operate until the fan off time is 

achieved. The oil burner will then resume operation and continue 

until the thermostat is satisfied. Restore the thermostat setting to a 

comfortable temperature.

To shut Down unit

Set the thermostat to the lowest possible setting.
Set the manual switch (if installed) in the Electrical Power Supply 

Line to "OFF".

Summary of Contents for HTL-90D

Page 1: ...Model with ECM Oil FiredWarm Air Furnaces INSTALLATION OPERATION MAINTENANCE MANUAL P N 240007799 Rev C 12 2009 ECR International 2201 Dwyer Avenue Utica New York 13504 USA www ecrinternational com R...

Page 2: ...HTL D HTL DV Oil Fired Warm Air Furnace ALL INSTALLATIONS MUST MEET ALL LOCAL PROVINCIAL STATE AND FEDERAL CODES WHICH MAY DIFFER FROM THIS MANUAL Read this complete manual before beginning installat...

Page 3: ...on Title Of Document Installation Requirements 4 Location Of The Unit 5 Controls Connections 6 Oil Burners 7 Combustion Chamber 8 Circulating Air Blower 8 Maintenance And Service 9 Operating Instructi...

Page 4: ...shipped assembled and pre wired The furnace should be carefully inspected for damage when being unpacked Heat Loss The maximum hourly heat loss for each heated space shall be calcu lated in accordanc...

Page 5: ...vided using a duct if necessary The duct opening shall have a free area of 1 square inches per 1 000 Btu h of total input rating of all appliances to be installed When a furnace is installed in a full...

Page 6: ...burner will be energized initiating a normal burner cycle Fan Timer Board and Limit Control Fig 5 Page 21 The United Technologies 1168 1 ECM HTLV D tap board has an adjustable fan on off delay that mu...

Page 7: ...flame retention head static plate and temperature rise the furnace may be fired at an ideal rate for a wide range of structures Refer to Tables 3A B and C page 11 and the furnace rating plate to deter...

Page 8: ...ed plenum duct systems The motor RPM and air CFM delivery will vary automatically on ECM motor equipped models to accommodate conditions within the usual range of external static pressures typical of...

Page 9: ...y All electrical connections should be checked to ensure tight con nections Safety controls such as the high limit controls should be tested for functionality The fan control should be checked to ensu...

Page 10: ...and continue until the thermostat is satisfied Restore the thermostat setting to a comfortable temperature NOTICE IF THE FURNACE IS TO BE SHUT DOWN FOR AN EXTENDED PERIOD OF TIME CLOSE THE OIL SUP PL...

Page 11: ...00 PSIG 1 20 USGPH F6 2 in Table 3B Beckett NX Oil Burner Set Up Beckett NX Series Oil Burners For use with chimney vented units only Furnace Model Output BTU Hr Burner Model Nozzle Pump Pressure Flow...

Page 12: ...ne screw Turn the adjustment screw clockwise to decrease the com bustion air and counter clockwise to increase the combustion air Re tighten the spline screw after obtaining the proper setting Refer t...

Page 13: ...num take offs and the trunk ducts Temperature rise value is listed on the system rating plate Perform a smoke spot test The smoke spot should not exceed No 1 on the Bacharach Scale After the air adjus...

Page 14: ...c 0 2 0 3 0 4 0 5 0 6 HTL D 90 120 100 10 DD 1 2 HP 7 70 F High 1639 1581 1507 1440 1374 Med High 1544 1493 1429 1366 1300 Med Low 1158 1144 1121 1084 1040 Low 766 743 703 696 661 HTL D 120 140 120 1...

Page 15: ...abinet Plenum Openings Flue Diameter Filter Shipping Weight LB Width Depth Height Supply Return Type Size Side Bottom HTL D HTLV D 22 30 3 4 58 20 x 20 14 x 22 14 x 22 6 Permanent 16 x 25 x 1 270 HTL...

Page 16: ...2 SW3 ADJUST POS CFM SW4 DELAY POS INPUT USGPH DIP Switch Position DIP Switch Position 1 2 1 2 OFF OFF A 0 OFF OFF A 1 00 ON OFF B 15 ON OFF B 1 10 OFF ON C 15 OFF ON C 1 20 ON ON D N A ON ON D 0 85...

Page 17: ...UT USGPH DIP Switch Position DIP Switch Position 1 2 1 2 OFF OFF A 0 OFF OFF A 1 00 ON OFF B 15 ON OFF B 1 10 OFF ON C 15 OFF ON C 1 20 ON ON D N A ON ON D 0 85 ECM Blower HTLV D NOTICE SW1 HEAT AND S...

Page 18: ...18 Wiring Diagrams Figure 6 Chimney Vent Burner Wiring Diagram HTL D HTLV D...

Page 19: ...adjustments can be made by moving the dipswitch settings on the timer control board for fan off delay To check the operation of the limit switch shut off power to the furnace Temporarily remove the n...

Page 20: ...over state Continues to spark for 10 sec Provides continuous spark after flame is sensed to assure that burner remains lit Turns on LED diagnostic light Starts carryover timer a Flame and call for he...

Page 21: ...21 Oil Primary Control Sequence of Operation Figure 7 United Technologies 1158 120 Fan Timer Board HTL D Figure 8 United Technologies 1168 1 ECM Tap Board HTLV D...

Page 22: ...22 Oil Primary Control Sequence of Operation...

Page 23: ...23 Oil Primary Control Sequence of Operation Table 9 1158 120 Electronic Fan Timer Board Eft Detailed Sequence Of Operation...

Page 24: ...primary control is in the run state by pressing the reset button The LED diagnostic light will flash the following code Table 10 Cad Cell Resistance Flashes Resistance in Ohms 1 Less than 400 2 Betwee...

Page 25: ...ES SARY PRECAUTIONS TO PREVENT ELECTRICAL SHOCK OR EQUIPMENT DAMAGE Preliminary Checks Make sure that limit switches are closed and those contacts are clean Check for line voltage power on the oil pri...

Page 26: ...26 Oil Primary Control Troubleshooting Table 11 Oil Primary Control TROUBLESHOOTING continued from previous page...

Page 27: ...27 Oil Primary Control Troubleshooting Table 11 Oil Primary Control TROUBLESHOOTING continued from previous page Table 12 System and General Trouble Shooting...

Page 28: ...light a maximum of 1500 in the presence of light Ensure that room light is not leaking into the cad cell compartment See diagnostic light section Furnace starts but cuts out requiring manually resett...

Page 29: ...29 Oil Primary Control Troubleshooting Table 12 System and General Trouble Shooting continued from previous page Check Blower fan speed...

Page 30: ...s if not obvious Where the oil shut off valve from the oil storage tank 3 is located How to operate the thermostat and other related ac 4 cessories How to operate the manual reset button on the 5 prim...

Page 31: ...31 Homeowner s Reference Table...

Page 32: ...s ECM Control HTLV 240005742 Wire Harness ECM Supply HTLV 32 240005330 Transformer 33 12240 6 Draft Regulator Ref No Part No DESCRIPTION 34a 240007760 Oil Burner Assembly Beckett AF76XN 29689 Burner M...

Page 33: ...33 PARTS LISTING HIGHBOY MODEL HTL D AND HTLV D Figure 9 Model HTL D and HTLV D...

Page 34: ...34 HTL D HTLV D Oil Fired Warm Air Furnace NOTES...

Page 35: ...35 HTL D HTLV D Oil Fired Warm Air Furnace...

Page 36: ...36 HTL D HTLV D Oil Fired Warm Air Furnace ECR International 2201 Dwyer Avenue Utica New York 13504 USA www ecrinternational com...

Reviews: