CH Settings
C H
S E T T
I
N G S
▲
W a r m
W e a t h e r
S h u t
d o w n
T e m p
7 0 ° F
▼
Allowed Range: 35°F to 100°F (2°C to 38°C)
Default Setting: 70°F (21°C)
If outdoor temperature is greater than Warm Weather
Shutdown Temperature, demand for CH blocked and pumps
stopped.
C H
S E T T
I
N G S
▲
R e s e
t
C u r v e D e s i g n
B o
i
l
e
r
1 8 0 ° F
O u t
d o o
r
2 5 ° F
▼
Allowed Boiler Range: 60°F to 195°F (40°C
to 91°C)
Default Boiler Setting:180° F (82°C)
Boiler capable of operating in Outdoor Reset Mode when
included Outdoor Sensor is connected and proper CH Mode
selected.
If CH Mode = 1, ‘Outdoor Temperature Reset with Thermo-
stat’ or 2, ‘Full Outdoor Reset’ boiler will adjust CH set point
proportional to outdoor temperature as defi ned by Outdoor
Reset Curve below.
Outdoor reset curve adjusted by modifying Design and Mild
Weather reference temperatures. See points A & B of Reset
Curve below.
Calculated CH set point always limited between ‘Reset Curve
Boiler Minimum/Maximum’ temperatures. See points C & D
of Reset Curve below.
Figure A-2 Outdoor Reset Curve
Note:
Modes only function when outdoor temperature sensor
•
connected.
If ‘Open’ outdoor sensor detected CH set point equal to
•
‘Boiler Reset Curve Design’ temperature.
Outdoor temperature used for CH set point calculation
•
measured once a minute and averaged with
previous measurement to compensate for rapid outdoor
temperature variations.
C H
S E T T
I
N G S
▲
R
. C u
r
v e
M i
l d
W e a t h .
B o
i
l
e
r
7 0 ° F
O u t
d o o
r
7 0 ° F
▼
C H
S E T T
I
N G S
▲
R e s e
t
C u r v e
B o
i
l
e
r
M i n
0 7 0 ° F
B o
i
l
e
r
M a x
1 8 0 ° F
▼
Allowed Min. Range: 40°F to 180°F (4°C to 82°C)
Default Min. Setting: 70°F (21°C)
Allowed Max. Range: 80°F to 195°F (27°C to 91°
C)
Default Max. Setting: 180°F (82°C)
B
Allowed Boiler Range: 35°F to 120 F (2°C to
49°C)
Default Boiler Setting: 100°F (37°C)
Allowed Outdoor Range: 35°F to 85°F (2°C to
29°C)
Default Outdoor Setting: 70°F (21°C)
1 0 0
A
B
C
D
A
C
D
Summary of Contents for OLSSC-075
Page 45: ...45 13 TROUBLE SHOOTING...
Page 52: ...52 14 WIRING DIAGRAM 14 1 Connection Diagram...
Page 53: ...53 14 WIRING DIAGRAM 14 2 Schematic Diagram of Ladder Form...
Page 70: ...70 NOTES...
Page 71: ...71 Date Service Performed Company Name Tech Initials Company Address Phone...
Page 72: ...ECR International Inc 2201 Dwyer Avenue Utica NY 13504 4729 web site www ecrinternational com...