The  display  shows:

1234567890123456

The cursor blinks over the ‘1’ digit . If we want the relay to be activated by lets say 
zones  1,2,3,4,5  and    6    press    the’1’  key  (yes)  6  times.  The  cursor  is  moved  6 
positions to the right and  is  positioned over  the ‘7’. Press  the  ‘2’  key (no) 10  times  
and  the  display will show:

1234567890123456

Pressing  ‘ENTER’ will activate the selection. The relay will only be  activated  when 
one  of    the  preselected  zones  (ticked)  issues  an  alarm.  We  can  also  adjust  the   
operation  time  and  the  time  to  operate  delay  as  described  earlier.

ACTIVATE FROM

TWO ZONES (AND) 

4.

The  relay is activated when 2 preselected zones issue an 
alarm  .If  this  method  of  activation  is  selected  the  by 
pressing  ‘ENTER’ we must  select  the  desired  zones on  
the  next  menu.

The  Display  shows:

1234567890123456

The  cursor blinks over the ‘1’. If  we  want  the  relay  for  example  to  be  activated 
by zones 5 and 6 the press the ‘2’ key for 4 times. The curcors shifts 4 places to the   
right  and is positioned over the ‘5’. Press the ‘1’ key (yes) 2 times and  the  display  
shows:

1234567890123456

By pressing ‘ENTER’ the setting is activated . The relay will be activated only  if  both 
zones 5  and  6  issue and alarm. We can also adjust the operation time and the time  
to  operate  delay  as  described  earlier.

The  second  device  that  can  be  programmed  is  the  FAULT relay. 
We  select  it  by  pressing  ‘ENTER’.

CONFIGURE

FAULT RELAY    1

ACTIVATE FROM

GENERAL FAULT

After  ‘ENTER’  is  pressed  the  activation  method  is 
shown.(default=GENERALl  FAULT)  If  we  want  to 

alter  the  activation  method  we  must    follow  exactly    the  same  procedure  as 
described  earlier  for  the  programming  of  the  ALARM  relay.  The    options    and   
settings  are  identical.

CONFIGURE
SIREN          1

ACTIVATE FROM

GENERAL ALARM

We can   also   program   the   siren   output. We   can   
select  using  the  ‘ FAULT EVENTS’ key 

Select the required output using the numeric keypad and by pressing ‘ENTER’ we can se

e

 it’s 

activation method (default=general ALARM). If  we  want to change the activation method press 
the ’FAULT EVENTS’ key and ‘ENTER’. The options available are. “ACTIVATED BY GENERAL 
ALARM”  and  “ACTIVATED  BY  ZONES(OR)”.  The  functions  of  the  setting  are  the  same  as 
described earlier for the ALARM relay. With the option “DURATION” we can select  if the output 
will have a permanent or an  interruptible  operation. The  settings  are  the  following: 
0= permanent operation

1 = interruptible operation with  3 seconds ΟΝ - 5 seconds OFF

15 

from

 21

921116000

Date

File

Code

Page

921116000_09_016

13/03/2013

Summary of Contents for BS-116

Page 1: ......

Page 2: ...6 3 User instructions 7 Programming tests information 7 1 Tests 7 2 Programming 7 3 Information 7 4 Deactivation 7 5 Activation 7 6 History record deletion 7 7 Automatic unit recognition 7 8 Setting...

Page 3: ...tection control and programming device Indication device repeater 16 Relay device Extinguishing device with adjustable delay Public address megaphone device with microphone Type Description BS 114 BS...

Page 4: ...anel can also accept a BS 620 megaphone driving device Any configuration between the minimum and maximum described is possible In this way a fire detection panel with the required capabilities can be...

Page 5: ...No 2 No 3 BS 116 16 64 Repeater BS 115 No 2 Repeater BS 115 No 3 BS 116 16 64 BS 116 16 64 BS 116 16 64 BS 118 fire extinguishing device No 8 Figure 2 BS 118 fire extinguishing device No 1 Control key...

Page 6: ...1 detector base on zone 1and connecting 2 bases of detectors on zone 2 One detector also has a BS 572 remote LED indicator connected to it Detector base Detector base 5 6 IN IN OUT OU T R IN IN OUT OU...

Page 7: ...st action that the BS 114 control keyboard must take is to recognize all the external devices that are connected to the network If the ENTER key is pressed then the display shows Each panel has the re...

Page 8: ...accessed Level 3 Level 3 operation are operations and setting that are done by the installation technician and need the technician code service code in order to be accessed All operations are done usi...

Page 9: ...nged with another 4 digit code if it is required In order to enter level 2 user level we must follow the following procedure Press the ENTER key The Display shows If the 0 key is pressed 4 time then t...

Page 10: ...ENTER ENTER ENTER ENTER ENTER ENTER ENTER ENTER The detectors are reset the LEDs are tuned off the sirens are silenced and the relays are deactivated After 15sec The panel enters normal operation A ma...

Page 11: ...more information press the FAULT EVENTS key After correcting all errors we must RESET the system Press the ENTER key enter the 4 digit code select SYSTEM RESET from the menu and press ENTER The Displ...

Page 12: ...nician code service code is required This is preset to 1111 but can be changed to any other 4 digit code In order to access level 3 operations follow the procedure described bellow ENTER YOUR CODE SEL...

Page 13: ...EST MODE SIREN 1 The setting 2 DEACTIVE blinks If the 1 key is pressed then the output is activated and the setting 1 ACTIVE starts to blink To deactivate the output press the 2 key SIREN 1 1 ON 2 OFF...

Page 14: ...red panel and press ENTER The default activation method is shown If we want to change the activation method then we must press the FAULT EVENTS key The display shows Press ENTER and using the FAULT EV...

Page 15: ...only if both zones 5 and 6 issue and alarm We can also adjust the operation time and the time to operate delay as described earlier The second device that can be programmed is the FAULTrelay We selec...

Page 16: ...hing module that we want to adjust the delay 1 120 seconds Programming the repeater panel functions CONFIGURE REPEATER 1 If a BS 115 is installed then using this selection we can adjust the permissibl...

Page 17: ...operation voltage Two readings are available GOOD or LOW INFORMATION BATT OF PANEL 1 Select using the numeric keypad and the ENTER key the required panel in order to view its battery voltage After a 2...

Page 18: ...23456 DISABLE ALARM RELAY 1 With the numeric keypad and the ENTER key we select the required ALARM relay The Display shows And the relay is deactivated ALARM RELAY 1 IS DISABLED DISABLE FAULT RELAY 1...

Page 19: ...that were previously deactivated are now activated ENABLE ZONES OF PANEL 1 With the numeric keypad and the ENTER key select the required panel The Display shows ENABLE ZONE 01 With the numeric keypad...

Page 20: ...activated 1234567890123456 7 6 History record deletion The sixth selection of the technicians menu is If ENTER is pressed then the history record of the system is deleted All ALARM and FAULT events a...

Page 21: ...RESET If we try to program an option on a device that is not on the network then the system issues the following message on the display SET SERVICE PHONE SERVICE PHONE UNIT IS NOT CONNECTED 220 240 VA...

Reviews: