Programming zone relays. I
f
a BS-117 relay module is connected we can select.
CONFIGURE
RELAY (1/64) 01
Using the numeric keypad and pressing enter we can select the relay
that will be programmed.
1 = interruptible operation with 3 seconds ΟΝ - 5 seconds OFF.
2 = interruptible operation with 10 seconds ΟΝ - 5 seconds OFF.
3 = interruptible operation with 5 seconds ΟΝ - 15 seconds OFF.
4 = interruptible operation with 1 seconds ΟΝ - 1 seconds OFF.
From the delay option we can adjust the time that the selected output will be activated
after the alarm is issued. This delay can be between 1 and 255 seconds.
Programming the start to extinguish delay. If a BS-118 is installed then th
i
s option is used
CONFIGURE
F-EX RELAY 1
for
activation delay of the Delay relay in each fire extinguishing
module. Using the numeric keypad and the ‘ENTER ‘ key we select the fire
extinguishing module that we want to adjust the delay.
(1 - 120 seconds).
Programming the repeater panel functions.
CONFIGURE
REPEATER 1
If a BS-115 is installed then using this selection we can adjust the
permissible functions that will be done with it. Using the keyboard and
‘ENTER’ we select the repeater panel that we want to adjust if it is
going to have the capability of evacuation, the capability of resetting the
system or the capability of silencing the sirens.
Programming the internal buzzer. With this option we can adjust the sound mode of the internal
buzzer (
selecting 0 or 1)
.
CONFIGURE
BUZZER 1
Resetting to default factory setting. If the ‘ ENTER ’ key is pressed and after the system warns
and asks
for confirmation it reset all settings to factory defaults and detects all the
devices that are connected on the communication line.
DEFAULT PARAMs
SETTINGS
Programming the internal buzzer. With this option we can adjust the sound mode of the internal
buzzer (
selecting 0 or 1)
.