background image

CONTENTS

1. Preface

2. Device Types

3. Configuration selections

4. Connections

5.Starting configuration (Setup)

6. Operation procedures

6.1 Operation level 1
6.2 Operation level 2
6.3 User instructions

7. Programming - tests - information

7.1 Tests
7.2 Programming
7.3 Information
7.4 Deactivation
7.5 Activation
7.6 History record deletion
7.7 Automatic unit recognition
7.8 Setting the user code
7.9 Setting the service code
7.10 Setting the service telephone

Technical characteristics

from

 21

921116000

Date

File

Code

Page

921116000_09_016

13/03/2013

Summary of Contents for BS-116

Page 1: ......

Page 2: ...6 3 User instructions 7 Programming tests information 7 1 Tests 7 2 Programming 7 3 Information 7 4 Deactivation 7 5 Activation 7 6 History record deletion 7 7 Automatic unit recognition 7 8 Setting...

Page 3: ...tection control and programming device Indication device repeater 16 Relay device Extinguishing device with adjustable delay Public address megaphone device with microphone Type Description BS 114 BS...

Page 4: ...anel can also accept a BS 620 megaphone driving device Any configuration between the minimum and maximum described is possible In this way a fire detection panel with the required capabilities can be...

Page 5: ...No 2 No 3 BS 116 16 64 Repeater BS 115 No 2 Repeater BS 115 No 3 BS 116 16 64 BS 116 16 64 BS 116 16 64 BS 118 fire extinguishing device No 8 Figure 2 BS 118 fire extinguishing device No 1 Control key...

Page 6: ...1 detector base on zone 1and connecting 2 bases of detectors on zone 2 One detector also has a BS 572 remote LED indicator connected to it Detector base Detector base 5 6 IN IN OUT OU T R IN IN OUT OU...

Page 7: ...st action that the BS 114 control keyboard must take is to recognize all the external devices that are connected to the network If the ENTER key is pressed then the display shows Each panel has the re...

Page 8: ...accessed Level 3 Level 3 operation are operations and setting that are done by the installation technician and need the technician code service code in order to be accessed All operations are done usi...

Page 9: ...nged with another 4 digit code if it is required In order to enter level 2 user level we must follow the following procedure Press the ENTER key The Display shows If the 0 key is pressed 4 time then t...

Page 10: ...ENTER ENTER ENTER ENTER ENTER ENTER ENTER ENTER The detectors are reset the LEDs are tuned off the sirens are silenced and the relays are deactivated After 15sec The panel enters normal operation A ma...

Page 11: ...more information press the FAULT EVENTS key After correcting all errors we must RESET the system Press the ENTER key enter the 4 digit code select SYSTEM RESET from the menu and press ENTER The Displ...

Page 12: ...nician code service code is required This is preset to 1111 but can be changed to any other 4 digit code In order to access level 3 operations follow the procedure described bellow ENTER YOUR CODE SEL...

Page 13: ...EST MODE SIREN 1 The setting 2 DEACTIVE blinks If the 1 key is pressed then the output is activated and the setting 1 ACTIVE starts to blink To deactivate the output press the 2 key SIREN 1 1 ON 2 OFF...

Page 14: ...red panel and press ENTER The default activation method is shown If we want to change the activation method then we must press the FAULT EVENTS key The display shows Press ENTER and using the FAULT EV...

Page 15: ...only if both zones 5 and 6 issue and alarm We can also adjust the operation time and the time to operate delay as described earlier The second device that can be programmed is the FAULTrelay We selec...

Page 16: ...hing module that we want to adjust the delay 1 120 seconds Programming the repeater panel functions CONFIGURE REPEATER 1 If a BS 115 is installed then using this selection we can adjust the permissibl...

Page 17: ...operation voltage Two readings are available GOOD or LOW INFORMATION BATT OF PANEL 1 Select using the numeric keypad and the ENTER key the required panel in order to view its battery voltage After a 2...

Page 18: ...23456 DISABLE ALARM RELAY 1 With the numeric keypad and the ENTER key we select the required ALARM relay The Display shows And the relay is deactivated ALARM RELAY 1 IS DISABLED DISABLE FAULT RELAY 1...

Page 19: ...that were previously deactivated are now activated ENABLE ZONES OF PANEL 1 With the numeric keypad and the ENTER key select the required panel The Display shows ENABLE ZONE 01 With the numeric keypad...

Page 20: ...activated 1234567890123456 7 6 History record deletion The sixth selection of the technicians menu is If ENTER is pressed then the history record of the system is deleted All ALARM and FAULT events a...

Page 21: ...RESET If we try to program an option on a device that is not on the network then the system issues the following message on the display SET SERVICE PHONE SERVICE PHONE UNIT IS NOT CONNECTED 220 240 VA...

Reviews: