BS-116 connection
ATTENTION
!!
ONLY 4 PANELS BS-116 CAN
BE CONNECTED IN ONE
INSTALLATION
.
To connect
the panels use ONLY the +A
and -A terminals. DON’T USE the
+
and
-
terminals
.
BS
-116
panel
BS
-116
panel
BS
-116
panel
BS
-116
panel
The maximum possible configuration consists of one BS-114 control keyboard,
four
BS-116
panels , three BS-115 repeaters,
four
BS-117 relay devices
and eight
BS-118 extinguishing
devices. Each device has it’s own address number. The connection between all of these
devices is shown in figure 2. Each panel can also accept a BS-620
m
egaphone driving
device.
Any configuration between the minimum and maximum described is possible. In this way a
fire detection panel with the required capabilities can be configured.
Figure 1
Connection of a BS-114 control keyboard with a BS-116 panel
BS-114
Programming and
control keyboard
BS-116
Fire detection panel
-
Connection between panels.
The make a network between pan
only the +A, -A must be connected
.
Below picture shows
the connection between panels.
Attention!!! To give an address to each panel use the dip-switches as shown in the
following diagram (Address 1,2,3 and 4).
A
A
A
A
A
A
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
A
A
Address
1
Address
2
Address
3
Address
4
921116000_09_016
13/03/2013
A
A
A
A
S
ir
e
n 1
S
ir
e
n 2
JP 1
J 6