Besides the terminal blocks mentioned the panel also has the following output:

24V uninterruptible :

 A 24Vdc uninterruptible power output that does not break in the event 

of a panel reset. It can be used to power electromagnetic door latches.

Relay  ALARM  : 

A  voltage  free  relay  contact  that  is  activated  when  a  zone  on  the  panel 

issues an  alarm.

Relay FAULT : 

A voltage free relay contact that is activated when the panel issues an error 

or a fault.
The panel also has 2 cables for connecting the battery. The cable with the red connector  is 
for connecting the positive (+) terminal of the battery and the cable with the black connector 
is for   connecting the negative (-) terminal of the battery. 

5. Starting configuration( Setup)

After all the connections to the panel are finished we can connect the battery and the 230V 

AC

 power supply.

The  first  action  that  the  BS-114  control  keyboard  must  take  is  to  recognize  all  the  external 
devices  that  are  connected  to  the  network.  If  the  ENTER  key  is  pressed  then  the  display 
shows

:

Each  panel  has  the  required  terminal  blocks  for  connecting  2  siren  circuits,    bells  or  other 
output  devices  that  operate  with  24Vdc.  Each  circuit  can  power  devices  with  a  maximum 
consumption of 600mA. Each of these circuits has a pre-fitted terminal resistor (5K6). This 
resistor  is  removed  and  placed  on  the  last  siren  or  it  is  left  in  it’s  place  if  the  circuit  is  not 
used. The connections on both of these circuits are identical.

F

igure 6. 

Connecting  3 BS-531 sounders with beacon on the SIREN 1 output circuit.

When connecting these device to the circuit ensure that the polarity is right.                

SIREN 1

SIREN 2

5

Κ

6

5

Κ

6

Terminal

resistor

Terminal

resistor

BS-531

Sounder

 with

beacon

GND

12V

24V

BS-531

Sounder

with

 beacon

GND

12V

24V

BS-531

Sounder 

with 

beacon

GND

12V

24V

ENTER YOUR CODE

----

from

 21

921116000

Date

File

Code

Page

921116000_09_016

13/03/2013

Summary of Contents for BS-116

Page 1: ......

Page 2: ...6 3 User instructions 7 Programming tests information 7 1 Tests 7 2 Programming 7 3 Information 7 4 Deactivation 7 5 Activation 7 6 History record deletion 7 7 Automatic unit recognition 7 8 Setting...

Page 3: ...tection control and programming device Indication device repeater 16 Relay device Extinguishing device with adjustable delay Public address megaphone device with microphone Type Description BS 114 BS...

Page 4: ...anel can also accept a BS 620 megaphone driving device Any configuration between the minimum and maximum described is possible In this way a fire detection panel with the required capabilities can be...

Page 5: ...No 2 No 3 BS 116 16 64 Repeater BS 115 No 2 Repeater BS 115 No 3 BS 116 16 64 BS 116 16 64 BS 116 16 64 BS 118 fire extinguishing device No 8 Figure 2 BS 118 fire extinguishing device No 1 Control key...

Page 6: ...1 detector base on zone 1and connecting 2 bases of detectors on zone 2 One detector also has a BS 572 remote LED indicator connected to it Detector base Detector base 5 6 IN IN OUT OU T R IN IN OUT OU...

Page 7: ...st action that the BS 114 control keyboard must take is to recognize all the external devices that are connected to the network If the ENTER key is pressed then the display shows Each panel has the re...

Page 8: ...accessed Level 3 Level 3 operation are operations and setting that are done by the installation technician and need the technician code service code in order to be accessed All operations are done usi...

Page 9: ...nged with another 4 digit code if it is required In order to enter level 2 user level we must follow the following procedure Press the ENTER key The Display shows If the 0 key is pressed 4 time then t...

Page 10: ...ENTER ENTER ENTER ENTER ENTER ENTER ENTER ENTER The detectors are reset the LEDs are tuned off the sirens are silenced and the relays are deactivated After 15sec The panel enters normal operation A ma...

Page 11: ...more information press the FAULT EVENTS key After correcting all errors we must RESET the system Press the ENTER key enter the 4 digit code select SYSTEM RESET from the menu and press ENTER The Displ...

Page 12: ...nician code service code is required This is preset to 1111 but can be changed to any other 4 digit code In order to access level 3 operations follow the procedure described bellow ENTER YOUR CODE SEL...

Page 13: ...EST MODE SIREN 1 The setting 2 DEACTIVE blinks If the 1 key is pressed then the output is activated and the setting 1 ACTIVE starts to blink To deactivate the output press the 2 key SIREN 1 1 ON 2 OFF...

Page 14: ...red panel and press ENTER The default activation method is shown If we want to change the activation method then we must press the FAULT EVENTS key The display shows Press ENTER and using the FAULT EV...

Page 15: ...only if both zones 5 and 6 issue and alarm We can also adjust the operation time and the time to operate delay as described earlier The second device that can be programmed is the FAULTrelay We selec...

Page 16: ...hing module that we want to adjust the delay 1 120 seconds Programming the repeater panel functions CONFIGURE REPEATER 1 If a BS 115 is installed then using this selection we can adjust the permissibl...

Page 17: ...operation voltage Two readings are available GOOD or LOW INFORMATION BATT OF PANEL 1 Select using the numeric keypad and the ENTER key the required panel in order to view its battery voltage After a 2...

Page 18: ...23456 DISABLE ALARM RELAY 1 With the numeric keypad and the ENTER key we select the required ALARM relay The Display shows And the relay is deactivated ALARM RELAY 1 IS DISABLED DISABLE FAULT RELAY 1...

Page 19: ...that were previously deactivated are now activated ENABLE ZONES OF PANEL 1 With the numeric keypad and the ENTER key select the required panel The Display shows ENABLE ZONE 01 With the numeric keypad...

Page 20: ...activated 1234567890123456 7 6 History record deletion The sixth selection of the technicians menu is If ENTER is pressed then the history record of the system is deleted All ALARM and FAULT events a...

Page 21: ...RESET If we try to program an option on a device that is not on the network then the system issues the following message on the display SET SERVICE PHONE SERVICE PHONE UNIT IS NOT CONNECTED 220 240 VA...

Reviews: