Other outputs and their use
The panel has the following outputs:
-
Output AUX.
This is an auxiliary power output (between «-» and «+») that has the capability of providing
20Vdc for maximum load of 300mΑ.
-
Connectors F_OUT.
Open collector output. If there is a general fault (Fault) it is enabled (0V).
NOTE The maximum drawn from output “AUX” must not be more than 300mA.
Network connection
It is possible to have network of panels. In each network, each panel has a unique address.
The central panel has address 1 and sub-panels have address from 2 to 16. The figure below shows the network
connection.
The interface cable is two cable twisted. The connection topology is parallel, for example should the cable from one
table to go to another and there are no interconnections
Caution resistors 120Ohm / 0,5 W should be placed at the beginning and end of the cable.
Figure
8
: Netowrk connections