BS-657        OPTICAL SMOKE AND THERMAL DETECTOR

Page 2 from 2

1. IN-OUT -L :

 It  is  connected  to  the zone of  the  panel or  to the (

IN-OUT -L

) contact  of  the  

previous  detector.

4. IN +L : 

It   is   connected   to   the zone of   the   panel or   to the (

OUT +R

) contact   of   the   previous   

detector.

3. OUT +R  and -R :

 It  is  connected  with  BS-572.

1. Detach the detector from it’s base by turning it anticlockwise until the side marks are aligned.

3. Connect the power cables (respect to polarity) according to the installation requirements (figure 
1,2).

2. Install the base with the included mounting parts (point 5).

Power the device and after 3-5 seconds will be ready to operate. 

2. OUT +R :

 It is connected to the next detector (

IN +L

)  or  if  it  is  the  last  one  to  the  terminal resistor.

CONNECTION

4. Place carefully the detector, so as to align the side marks and turn it clockwise all the way.  

Mounting base

Figure 1.

5

5

R

+

-R

O

U

-

-L

NI

T

 +

U

R

O

N

  +

L

I

Installation procedure

2

Indication marks

Page 1 from 2

Connection 
with external
LED BS-572

Term

inal

resis

tor

Figure 2

If the power of the detectors is turned off, wait for 3-5 seconds before you turn the power on again. 

You can connect up to 30 detectors BS-657 on each zone.

Connection

Fr om z one

of the pa ne l

-R

O

U

-

-L

NI

T

 +

U

R

O

N

  +

L

I

-R

O

U

-

-L

NI

T

 +

U

R

O

N

  +

L

I

sten

a

f

u

n

n

e

f

t

as

1

Indication 

LED

0.120dB/m and 58-62°C

20-30mA

IP20

EN 54-5, EN 54-7

50μA

160gr.

CLASS

A2R

The  detectors  BS-657  were  created  to  offer 
quick detection in case of fire. 

To  test  the  optical  detector  you  can  spray  a 
small  amount  of  smoke  into  the  detector’s 
chamber.  You  can  use  the  special  smoke 
device  A-752  of  our  company,  or  a  similar 
device. To check the thermal limit you need a 
special tool.

The detectors must be placed in the ceiling on 

They have two parts, one plastic base which is 
installed on the ceiling and the main unit of the 
detector  which  is  fastened  to  the  base  by  a 
simple turning to the right. The detectors have 
an indication led which lights continuously in 
case  of  fire  detection  until  there  is  a  reset 
signal from the panel. The indication led also 
flashes every 4 sec to indicate good operation. 
These  detectors  can  cooperate  with 
conventional fire alarm panels like BS-632 and 
BS-636.

It is advised to conduct a good operation test 
every  6  months  and  every  time  the  detector 
position is changed. 

NOTE

Before  installing  the  detector,  the  user  must 
read these instructions carefully and store this 
manual  for  future  reference.  The  BS-657  is 
optical smoke and thermal detector.

GENERAL

OPERATION CHECK 

It is essential to have good air circulation inside 
the detector. Therefore care must be taken so 
that the vents of the detector are not covered.

visible areas with no side obstacles and away 
from sides with no air circulation or strong air 
currents  and  vapors.  Each  detector  covers 

almost  50  m and  the  distance  between  two 
detectors  must  not  exceed  15m.  Also  the 
detectors  must  be  placed  away  from 
fluorescent tubes at least 50 cm.
The cables cross section must be from 0.5 to 

2

1.5mm .

ATTENTION!!

After the device is installed, care must be taken, 
so  that  the  detector  vents  are  not  blocked  by 
anything (i.e. dust, paint). Failing to do so will 
prevent  the  smoke  particles  to  enter  the 
detection chamber.
A f t e r  t h e  i n s t a l l a t i o n ,  i t  i s  t h e  s o l e 
responsibility of the user to maintain the 
detector for good operation.

Certification

The Rate of rise heat detetor BS-657 is 
certified from H.E.E.Q.A.C. Also 
H.E.E.Q.A.C. controls the production 
under CPR number: 

TECHNICAL CHARACTERISTICS

START UP POWER CONSUMPTION
STAND BY POWER CONSUMPTION

OPERATION VOLTAGE

SENSITIVITY
INDICATORS

ALARM POWER CONSUMPTION

PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE

DEGREES OF COVER PROTECTION

RELATIVE HUMIDITY

OUTPUT

TYPICAL WEIGHT 

EXTERNAL DIMENSIONS 

GUARANTEE

18-30V DC

150μA for 50 sec

Alarm LED

To panel / to external LED driver (BS-572)

103 (diam.) x 48 (height)

 mm

o

-10 to 60  C

Up to 95% 

2 years

921657000_09_002

921657000_09_002

Olympia Electronics guarantees the quality, condition and operation of the goods. The period of warranty 
is  specified  in  the  official  catalogue  of  Olympia  Electronics  and  also  in  the  technical  leaflet,  which 
accompanies  each  product. This  warranty  ceases  to  exist  if  the  buyer  does  not  follow  the  technical 
instructions included in official documents given by Olympia Electronics or if the buyer modifies the goods 
provided or has any repairs or re-setting done by a third party, unless Olympia Electronics has fully 
agreed to them in writing. Products that have been damaged can be returned to the premises of our 
company for repair or replacement, as long as the warranty period is valid.
Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the 
buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the 
buyer the transportation cost.

HEAD OFFICE

www.olympia-electronics.gr

P.C. 60300 P.O. Box 06 Εginio Pierias Greece

info@olympia-electronics.gr

72nd km. O.N.R. Thessaloniki-Katerini

Warranty

Warranty

EN-54-7: 2000 + A1: 2002 + A2: 2006

0848-CPR-017                                     15

BS-657

 

 

RATE OF RISE HEAT 

DETECTOR

EN-54-5: 2000 + A1: 2002

0848

60061 GREECE

KOLINDROS PIERIAS