OPERATION - USE

BS-685  and  BS-686  detectors  are  used  in 
combination  with  gas  panels  to  give  us  a   
warning  in  case  there  is  a  natural  gas  or  LPG 
gas  leak.

 

The  installation  must  be  done  by  a 

qualified  personnel.  Instructions  must  be  read 
before the installation.

Emergency  Actions

It  is  recommended  that  the  following  advice 
should  be  given  in  the  event  of  an  alarm 
sounding  or  the  smell  of  gas  even  without  an 
alarm:
Keep calm, and carry out the following actions, 
not  necessarily  in the order given:
-extinguish  all

 

flames,  including  smoking 

material.
- turn off all gas appliances.
- do not switch on or off any electrical equipment, 
including  the gas detection apparatus.
- turn off the gas supply at the gas main control 
and/or ( with a LPG supply) the storage tank.
-open  doors  and  windows  to  increase 
ventilation.
- do not use a telephone in the building where the 
presence of a gas is suspected.
If the alarm continues to operate, even after an 
alarm  resetting  action  where  appropriate,  and 
the  cause  of  the  leak  in  not  apparent  and/or 
cannot  be  corrected,  vacate  the  premises  and 
IMMEDIATELY  NOTIFY  the  gas  supplier    in 
order  that  the  installation  may  be  tested  and 

made safe, and any necessary repair carried out.

Placement

Depending on the monitored gas, the unit must be 
placed  with  the  sensor  downwards,  30cm  from 
the  ceiling  (for  methane,  natural  gas)  or  30cm 
from the floor (for propane, LPG).  The horizontal 
distance should not be more than 4 meters from 
the  probable  gas  leak  point  and  the  detectors 
must not be placed in humid or drafty areas.  
It is suggested that the detector is tested for good 
operation  every  6  months  or  if  it  is  changed 
position.
The unit must should not be sited:
- directly above cooking appliances
- directly above sink
- adjacent to extractor fans
- in  any outside location
-where the environmental conditions are outside 
the manufacturers operational specification.

Installation

In order to install the device you must first remove 
the  four  srews  (figure  1).  Then  with  the 
assisstance of figures 2 and 3 you can connect it 
to the  panel.

Connection  with  fire  panel  of  Olympia 
Electronics.

Terminals   ΖΟΝΕ are used to connect to zone of 
the  gas  panel,  as  shown  in  figure  2.  A  terminal 
resistor (5,6KÙ) should be installed on the end of 

BS-685  Waterproof LPG detector for conventional panels 
BS-686  Waterproof natural gas-methane detector for conventional panels

TECHNICAL CHARACTERISTICS

Thank you for your trust in our products  

Olympia Electronics - European manufacturer

Operation voltage

Average consumption

Sensitivity

Indicators
Degrees of cover protection

Produced in accordance with
Operation temperature range

Humidity

Dimensions

Sensor life time 
Weight

Guarantee

BS-686

BS-685

10-30V AC- DC ( Powered by panel)

0,5W ( 12VDC 40mADC, 24VDC 20mADC)

5-15 % L.E.L. Methane

5-15 % L.E.L. Propane

 alarm LED

IP 65

EN 50194-1, EN 50270

o

0 to 60  C

Up to 95% relative humidity

155 x 80 x 43 mm

5 years

150 gr

2 years