background image

Page

 

3 from

 

5

Figure 3. 

Connection diagram of a detector with a fire panel of other company.

Ζ

o

n

e

1

0

-3

0

V

D

C

Terminal Resistor

LED Alarm

Jumper for programming 
alarm latch mode

Fire panel 

Relay resistance
selection jumper

Sensitivity

The  BS-685  detectors  are  activated  when  the 
content of gas (propane), in the monitored area, 
exceeds  5  -  15%  of  the  lower  explosive  level 
(L.E.L). 
The  BS-686  detectors  are  activated  when  the 
content of gas (methane), in the monitored area, 
exceeds  5  -  15%  of  the  lower  explosive  level 
(L.E.L). 
The  devices  are  connected  to  24_M,  of  a  gas 
panel, as shown in figure 2. When a detector is 
activated,  it  gives  an  alarm  signal  to  the  gas 
panel.  The activation stops when: 
A) You push the test button or when you cycle the 
power of the detector (Alarm latch mode) (figure   
4).
B) You  push  the  test  button  or  the  gas  content 
drops below  5-15% of the L.E.L.  (Νο alarm latch 
mode) (figure 5).

Indication LEDS and Operation

When  first  installed,  you  must  wait  20  seconds 
until the sensor compensates to its surroundings. 
When the red LED is lit then the unit is in alarm 
mode.  Alarm  mode  can  be  triggered  from  the 
sensor of the unit. Figure 4 shows a connection 
diagram between 4 BS-685 or BS-686 and a gas 
panel.

Waterproofing of the device

The package contains a sealing gasket which is 
installed on the rim of the front cover in order to 
water-proof the unit.

Relay resistance Selection (JMP RELAY)

There is the capability to select the alarm relays 
resistance,  with  the  use  of  the  resistance 
selection  Jumper.  When  a  link  is  used  on  the 
jumper, then the used resistance is zero, and an 
external resistence may be used. If there is no 
link, then the on board resistence of 440 Ohm is 
used.

ATTENTION!!  The  devices  must  not  be 
tested using gas filled lighters because the 
sensor will be destroyed.

921686000_09_01

7

Reviews: