5.4.2
Change technician code
“
CHANGE TECH CODE
” option will display the screen on the right,
asking the technician to enter a new code for access level 3. After
inputting the code, the panel asks to enter the new code again for
confirmation.
WARNING
: Changing the technician’s code is an action that must be
taken responsibly. If the code is lost there is not any possible way to
reset the technician code back to default.
Figure5-39.Change tech code
5.4.3
External PCB function
“
EXTERN. PCB FUNCTION
” option is used to select the preferred
optional expansion functionality. The expansion adaptor may not be
pre-installed (optional), therefore in order to operate a mode must be
given via this menu. The available options are:
-
NONE (when no expansion card is installed)
-
PRINTER (when printer adaptor for A-200 printer is installed)
-
MODBUS (when MODBUS adaptor is installed)
Figure5-40.External PCB
5.4.4
Select MODBUS address
“
SELECT MODBUS ADDR.
” option is used to set current control
panel’s address for the MODBUS network. Available addresses are 1
to 247.
Figure5-41.Select MODBUS addr
5.4.5
Ethernet adaptor
“
ETHERNET ADAPTOR
” option displays a submenu displayed on the
screen on the right.
Figure5-42.Ethernet adaptor