5.4.8
Annual check date
“
ANNUAL CHECK DATE
” option indicates the next scheduled
maintenance date.
Figure5-48.Annual check date
5.4.9
Reset defaults
“
RESET DEFAULTS
” clears memory and restores all configurations
back to factory default values.
The only exceptions are certain hardware configurations:
Loops (enabled/disabled), External PCB function, Ethernet PCB
(enabled/disabled).
Figure5-49.Reset defaults
5.5
Clear events log
The “
CLEAR EVENTS LOG
” option deletes all event log entries in
the control panel. This option should be executed after every initial
installation so event logs during commissioning are cleared and real
time operation events are logged.
Figure5-50.Clear events log
5.6
Initializing alarm counter
The “
INIT. ALARM COUNTER
” option is used to reset the alarm
counter back to “0”. The number of recorded alarms can be seen in
“MENU > INFORMATION > ALARMS COUNTER”.
This option is only accessible with level 4 access, meaning that the
technician must have physical access to the dip-switch selector on
the back side of the CPU board and switch selector 1 to ON position.
After executing this function, dip-switch selector 1 shall be set back
to OFF position.
Figure5-51.Init. alarm counter