8.2
Functions
Similar to BSR-1001-2-4/MAR the BSR-1000/MAR has the same
functionality as far as the indicators, screen and keypad concerns, as well
as the Menu structure.The only difference is some functions limitation, i.e.
the screen on the right is shown on menus that repeaters cannot access,
preventing wrong actions.
Εικόνα8-1. Limited acces to repeaters
BSR-1000/MAR functions are:
Reset
Evacuate
Siren silence
Check current event
Check recorded event
Attention! In the BSR-1000/MAR repeater panel you can’t install any points.
8.3
Installation
Repeater installation should be carried out in the same way as in other BSR-100x/MAR series panels.
Follow the instructions on chapter 4 for the repeater installation.
8.4
Wiring
The connection of the repeaters is made through the RS-485 protocol. The existing network panel is used
for the connection of the repeaters. The panel network should be implemented by 1 master panel, up to 3
subpanels and up to 8 repeaters, up to 12 total panels in network. The wiring should be carried out
according to the instructions on chapter 4.5
8.5
Setup repeater network
The repeater has a default address 5. For proper operation it is necessary to setup the network panel.
Prior to any network setup, the address on each repeater and subpanel should be set and after that
address 1 on master panel should be set for network identification.
8.5.1
Setup repeater address
Repeater address is set from the
“TECHNICIAN MENU”
on the
submenu
“SETUP”
by selecting
“PANEL NETWORK”
. Select address
1 for the master panel, 2-3-4 for the subpanels and 5-6-7-8-9-10-11-12
for the repeater panels. Next select
“NETWORK SETUP”
and
“ENABLE”
. This procedure is repeated for every panel connected to
panel network.
Εικόνα8-2. Panel network address
ATTENTION! Do not set repeater address 5-12 in master panel – subpanels or master – subpanel
address 1-4 to repeater panel.