Date
22/4/2021
Document number
921100400_09_005
Page
12 of 71
12 / 71
2.6
Access Level Functions 1 (Access Level 1)
This level refers to the functions that a simple user can do directly via the keypad while on main screen.
No code (password) is required for these functions
-
“
BUZZER SILENCE
”
: On the event of a fault, or an alarm, if this key is pressed, the
built-in buzzer stops sounding. As long as the event is present, the buzzer makes a
short burst sound every 30 seconds. If a new event appears, the buzzer will start
sounding again.
-
“
LAMP TEST
”
: By pressing this key, all LED indicators are being lit for 5 seconds, in
order to confirm functionality.
-
“OVER
RRIDE DELAYS
”
: If alarm state is active and the delays are enabled, the user
can override the delays by pressing this key. The outputs will be activated instantly,
bypassing all user programmed delays.
-
“
VIEW ALARMS
”
: In alarm state, if this key is pressed, all current alarms are displayed.
More details are provided in the next paragraph.
-
“
VIEW FAULTS
”
: When there is one or more fault events, if this key is pressed, all
current faults are displayed. More details are provided in the next paragraph.
2.7
Basic access level menu 1 (Access Level 1)
When in the main screen, by pressing Enter key the screen displays the main menu as shown below:
Figure 2-5.Main menu
IMPORTANT!
When in alarm state, the first option will be “
CURRENT
ALARMS
”. When in prealarm
state,
the first option will be “
CURRENT
PREALARMS
”. When in fault state, the first option will be “
CURRENT
FAULTS
”. If there are disabled segments, the first option will be “
VIEW
DISABLEMENT
”. If more than the
states above are active, their options will appear in the priority order mentioned above.
Normally, on quiescent state, the available options will be those on figure 2-5 (Main menu)