5.3.4
Change point address
This option may be used in order to change a specific point’s address,
in purpose of replacement, adding new point or other modifications on
the installation.
This function will send a command to change the address of all
connected devices to the selected loop. Therefore, in order to change
a point’s address, connect the target point only, disconnect all other
points (
by removing the loop’s detachable terminal). You can use a
short 2-core cable to connect the
–L/+L contacts directly on +IN/-IN of
the point (no need for loop return).
When selecting this option, the system asks for the loop output to be
used for changin
g a point’s address. Make sure that you have
selected the same loop that you have temporarily removed all of its
other points. Select a loop and press Enter key.
Then the following screen on the right is shown. The “OLD” address,
indicates the current addr
ess of the connected point. The “NEW”
address indicates the selected address to be assigned. Use up/down
keys to select another address and Enter key to confirm command.
Figure5-21.Change point address
WARNING!
Do not use this function while more than one addressable points are connected to the
selected loop.
5.3.5
General resound
“
GENERAL RESOUND
” option will display the screen on the right.
By selecting YES, the general resound parameter is activated. This
means that after sending “
SIREN SILENCE
” command on an alarm
event, a new alarm event will trigger again the audible alarm signal,
leading to siren resounding.
By selecting NO, this parameter is inactive, meaning that when the
audible alarm is on silence, a new alarm event will keep the sirens
silent.
“
SIREN SILENCE / RESOUND
” key functionality is not altered by the
option above. Silencing and re-enabling manually the sirens is always
available.
Please note that when a network of panels has been installed, all
subpanels must have the same setting with the master panel.
Figure5-22.General resound
5.3.6
Conventional sirens
“
CONVENTIONAL SIRENS
” option will display the screen on the
right, in order to configure a conventional siren output, regarding
event trigger and delay. By default all conventional siren outputs are
enabled on general alarm.
First, the control panel asks for conventional siren output. Select the
output number (1 to 4) and press Enter to configure. The configuration
steps are appearing with the following order:
Figure5-23. Setup conv. sirens