Date
9/7/2018
File
BSR-2114/MAR
Document Number
921211401_09_002
Page
17 από 74
17
2.6
Access Level 1 functions
This level contains the functions that can by implemented by a normal user.
Figure 2-6 Access Level 1
functions
-
“Buzzer Silence”
: In case of an alarm, pre-alarm or fault and if button (1) is
pressed then the internal buzzer will stop. The buzzer sounds every 30 seconds
for all the duration of the event. If in this state the panel recognizes a new
event then the buzzer starts to sound.
-
“View Faults”
: Pressing this button when a fault condition is active will permit
us to see the current fault events. We will present this option in detail in the
next paragraph.
-
“Lamp Test”
: When the panel is in normal operation with no alarm, pre-alarm
or fault condition then by pressing this button (3) we can conduct a lamps test
which will light all the leds and the display in order to verify for good
operation.
2.7
Access Level 2 (User Functions)
This level contains all the functions that are required by the user of the system during an alarm, pre-alarm or fault condition.
These functions should be available only to the person that is responsible for the fire protection of the building.
The functions available by pressing a button are shown below.
Figure 2-7 User Functions
-
«Siren Silence/ Resound”:
Press this key to stop or
resound the sirens during and alarm event.
-
“Evacuate” :
Press this key to issue and evacuation
condition.
-
“Reset” :
Using this key permits us to reset the
system.
In order for the above function to take place, the access level 2 code must be inserted
Access level 2
2.8
Access levels 3 and 4 (Technical function)
Technical functions are done using the menu and will be described in detail in section 5.
TYPE IN YOUR CODE
----