background image

MAINTAINED EDGE EMERGENCY

ILLUMINATION SIGN WITH LEDS

92250300

1

_09_001

Page

 

1 from

 6

 CLD-30/NST

220-240V AC/50-60Hz

3h

24h

Overcharging and deep discharging protection

Charge LED / Test button

IP40

30m

3.6V/1.0Ah

45lm / 95lm 

EN 60598-1, EN 60598-2-22

, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3

, EN 1838

5   40  C

o

to

Up to 95% 

Aluminum

plexiglas, ABS/PC

310x240x51mm

3 years

 (1 

year for the battery

)

1060gr.

3.5W / 3.7VA

TECHNICAL CHARACTERISTICS

 

for LED MODULE Specs. see page 

2

)

(

OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIALS
EXTERNAL DIMENSIONS

 (

LxWxH)

TYPICAL WEIGHT
GUARANTEE

MAINS VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERY (Ni-Cd)

RECHARGING TIME

BATTERY PROTECTION
INDICATIONS/ CONTROL

MINIMUM EMERGENCY DURATION

DEGREES OF COVER PROTECTION

VIEWING DISTANCE 

PRODUCED IN ACCORDANCE WITH

LIGHT SOURCE INTENSITY (230V) / (emerg.)

GENERAL

o

These  luminaires  are  used  indoors 

(

ta  40 C

)

 

where emergency light is needed.
E a c h   l u m i n a i r e   m u s t   b e   p e r m a n e n t l y  
connected to mains power supply

.

In normal operation the led strip lights and the 
battery is charging.
In    case    of    a    mains    power    supply  failure   
the    luminaire    will    light  the  led  strip 
automatically  in  emergency  mode  (powered 
by  its  battery).    When  the    mains    power   
supply  is  restored the device turns to normal 
operation.

INSTALLATION

To  install  the  illumination  sign  you  must 
follow  the  installation  instructions  on  pages 
3,4,5 and 6.

NON 

MAINTAINED 

MAINTAINED 

OPERATION

There is an option to select the non maintained 
or maintained operation by placing the jumper to 
the appropriate place according to the

 

procedure on page

 4.

selection 

Test Button Function - 

 

,

 

 

Manual

 Test

As the luminary is in normal operation, by pressing 
the test button and holding it you can check the 
emergency operation of the luminary When you 
stop pressing the button the luminary returns to 
normal  operation.

The  manual  test  can  be 

conducted only if the mains power supply and 
the battery is connected. 

Indication  LED  status  (with  connected 
mains power supply).

Charge

On:

 

Good charge condition.

Οff:

 

No battery 

(

No charging current 

or disconnected battery

).

INDICATORS/CONTROLS

TEST

BUTTON

CHARGE

LED

Thank you for your trust in our products.  

Olympia Electronics -  European manufacturer

.

Summary of Contents for CLD-30/NST

Page 1: ...eration the led strip lights and the battery is charging In case of a mains power supply failure the luminaire will light the led strip automatically in emergency mode powered by its battery When the mains power supply is restored the device turns to normal operation INSTALLATION To install the illumination sign you must follow the installation instructions on pages 3 4 5 and 6 NON MAINTAINED MAIN...

Page 2: ...s of the same type by the manufacturer or by a competentperson t i in battery recycling points Donotincinerate The light source contained in this luminaire shall only be replaced by the manufacturer or his agent or a similar qualified person NOTE The light source is non user replaceable 5 In case of inactive use for a period greater than 2 months disconnect the battery by pulling outthebattery sco...

Page 3: ...m the respective steps of the electrical connections SURFACE MOUNTING ON A WALL single sided Install the included bracket on the wall page 4 and perform the respective steps of the electrical connections CEILING INSTALLATION Install the mounting base on the ceiling page 4 and perform the respective steps of the electrical connections HANGING INSTALLATION optional Install the mounting base tube on ...

Page 4: ... to support the marking panel 4 Ιnstall the battery s connector or replace the battery with a new one with its battery s connector to the appropriate P C B connector 5 Slide in carefully all the electronic parts take care of the battery cables 6 Refit the marking panel and fasten the removed screws in step 2 and then the screws of the step 1 Follow the step 3 and 4 of the installation instructions...

Page 5: ...nting accessories for installation Cable entry hole Place the included mounting screws for the flag mounting base Place the included mounting screws in these holes of the plastic bracket Install the mounting base with the two included screws A 1133 SET OPTIONAL AFTER REQUEST A 1134 SET INCLUDED IN THE PACKAGE If necessary place the included spacers to mount the base ...

Page 6: ... warranty ceases to exist if the buyer does not follow the technical instructions included in official documents given by Olympia Electronics or if the buyer modifies the goods provided or has any repairs or re setting done by a third party unless Olympia Electronics has fully agreed to them in writing Products that have been damaged can be returned to the premises of our company for repair or rep...