supply  and  the  battery  should  be  connected 
and  fully  charged

If  the  battery  is  not  fully 

charged

the  test  is  postponed

 

until  the 

battery  is  completely  charged.  If  during  this 
test, the autonomy is less than nominal then 
the  battery  fault  led  turned  on  continuously 
and the battery must be replaced. 

Back Up Operation

The  autonomous  duration  of  battery  during 
emergency  mode  is  at  least  180  minutes. 
During  emergency  mode,  a  light  source  test 
is also performed.

Resetting Errors

Push  the  Test  button  for  more  than  5 
seconds,  to  delete  all  the  indicated  LED 
errors.  Then    the  device  enters  regular

 

operation mode.

Indication  LED  status  (with  connected 
mains power supply).

Charge

 (Green LED)

 

On:

 

Good charge condition.

Οff:

 

No battery 

(

No charging current 

or disconnected battery

).

Fault (Red LED)

 

Οn

 

:

 

Faulty  LED  strip  (must  be  replaced)  or 

emergency  circuit  (must  be  checked  by  an 
authorized personnel).

Blink

 (

With Charge LED ON):

 Autonomy or 

low  battery  problem 

(the  battery  must  be 

replaced).

Οff:

 

LED strip and battery ok.

ΑΤΤΕΝΤΙΟΝ

!!!

1.  Operations  for  installation,  maintainance 
or  testing  must  be  done  by  authorized 
personnel only

.

2. 

The  device  must  be  connected  to  the 

m a i n s   p o w e r   s u p p l y   t h r o u g h   a   f u s e  
dependent  by  the  total  amount  of  the  line’s   
power load

.

3

In case of inactive use for a period greater 

than  2  months,  disconnect  the  battery  by 

pulling out the battery’s connector.

 

4

I s not allowed to discard batteries in to 

common  trash  bins,  they  must  be 
discarded  only 

t i

in  battery  recycling 

points.

 

Do not incinerate.

NOTE: 

LED=

 

Light Emitting Diode

LABELING EXPLANATION:
X: 

Self contained

1: 

Maintained

 (*)

A: 

Including test device

G: 

Internally illuminated 

 

90: 

1.5 hour duration

 

180: 

3 hours duration

NOTE!!

  T

he  installer  should  fill  in

,  on  the 

specification label,

 the letter 

G

 if the luminaire is 

used as a safety sign

.

(*) 

Maintained operation: The luminaire lights 

its illumination source, when it is powered by 
the mains power supply or not

Non Maintained operation: The luminaire 
lights its illumination source,

 

only in  power 

supply’s failure. 

Battery replacement

It  can  be  done  only  by  a  competent  person 
and after the mains interruption

.

1. 

Dismantle  the  device

 

(step  1  of

  the 

installation 

instructions)

.

2.  Disconnect  the  connector  and  remove  the 
old battery.
3.  Connect  the  new  battery  with  the  same 
type  (step 

4

  of  the  installation 

instructions

and

 

place it in the position of the old one.

4.  Follow  the  step 

6

  of  the  installation 

procedure and power the device

.

The light source contained in this luminaire shall only be replaced by the manufacturer, or his 

agent, or a similar qualified person.

NOTE! The light source is non-user replaceable.