STABILIZED POWER SUPPLY 12V DC

923024005_23_006

Page 1 from 2

TECHNICAL CHARACTERISTICS

OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIALS 

EXTERNAL DIMENSIONS 
TYPICAL WEIGHT

GUARANTEE 

OPERATION VOLTAGE

MAXIMUM POWER CONSUMPTION
SEALED LEAD ACID BATTERIES (Pb)
OUTPUT 

CHARGING TIME
AUTONOMY  (with maximum Load)

INDICATIONS LED’s

BATTERY PROTECTION

DEGREES OF COVER PROTECTION

PRODUCED IN ACCORDANCE WITH

REMOTE INPUT VOLTAGE RANGE

85-265V AC/50-60Hz

3 h

24 h

Mains/battery charging red LED, output activation green LED

From overcharge and full discharge

IP 42

2x12V/7Ah (not included)

Network: 13.5V/ 4A (max.) / Battery : 12V / 4 A 

 

(max.)

  6-30V DC / 1.5mA (maximum) 

163 VA

0 to 40  C

o

Up to 95% 

Bayblend FR3010, transparent polycarbonate

3 years (1 year for the battery)

5150gr.

300 x 95 x 230 mm

   GR-24/12-1

EN 55015, EN 61547, EN 60950-1, EN 61000-3-2, EN 61000-3-3

Thank  you  for  purchasing  this  product  of 
O l y m p i a   E l e c t r o n i c s .   A   E u r o p e a n  
manufacturer.

GENERAL

The  GR-24/12-1  is  a  stabilized  power  supply   
continuous operation that provides a voltage of 
12V DC  to independent devices (according to 
the device). The output network is stabilized to 
the 13,5 V DC with a maximum current 4Α. 
It  provides  continuous    power  to  the  external 
devices, with the incorporated power supply as 
long  as  the  mains  power  supply  does  not  fail. 
In case of mains failure the device gives power 
to  the  external  devices  from  the  included 
battery.
In  fire  detection  systems  it  is  used  when  the 
detector’s  power  consumption  is  greater  than 
the maximum panel that the panel can provide.
It  is  also  used  to  power  any  other  device  that 
require 12 V DC and autonomous operation. 
The  device  includes  the  SW1    switch  which 
activates  or  deactivates  the  output  as  long  as 
you desire. 
The  green  indication  LED  indicates  the  output 
status.  The  jumper  LOCAL/REMOTE  is  also 
used  according  to  the  input  REMOTE  in  the 
respective  terminal  blocks  and  concerns  the 
output  status.  If  no  external  device  to  control 
the  GR-24/24-1  output  is  connected  then  the 
jumper  must  be  placed  in  pins  1-2  and  the 
output  control  can  be  done  with  the  switch 
SW1.  If you want to control the output from an 
external device, 
then the jumper must be placed in pins 2-3, 

the  switch  SW1  in  the  ON  position

  and  the 

control  signal  must  be  connected  to  the 
REMOTE  terminal  blocks.  In  the  input,  when 
the  voltage  exceeds  6V,  then  the  GR-24/12-1 
output  is  active  and  when  the  voltage  remains 
under 6V the output remains deactivated.  

 

Autonomy calculation example

The  autonomy  of  the  device  is  proportional  to 
the  battery  (i.e  7Ah  for  GR-24/12-1  and 
inversely  proportional  to  the  consumption  of 
the number of detectors. If you want to connect 
10 devices that consume 200mA from the GR-
2 4 / 1 2 - 1 ,   t h e n   t h e   a u t o n o m y   w i l l   b e  
approximately  6  hours,  and  if  we  want  to 
connect  20  devices,  the  autonomy  will  be 
approximately  3  hours.  In  this  way  we  can 
calculate  how  many  detectors  will  connect  to 
the power supply and how much autonomy we 
have.  The  device  has  an  electronic  fuse  that 
protects its output from short circuits that could 
cause  serious  problems.

ΑΤΤΕΝΤΙΟΝ!!!

1. Operations for installation, maintainance or 
testing must be done by authorized personel 
only.
2. The device must be connected to the mains 
power supply thru a fuse dependent by the 
total amount of the line’s  power load.

When  activated  the 

electronic  safety  output  is  disconnected 
permanently and for restoring the functioning of 
the device will be restored in a shortcircuit and 
to disconnect the network and the battery for a 
few  seconds.Immediately  after  can  function 
normally.