Page
1 from
4
923270000_09_00
4
GENERAL
o
These devices are used indoors
(
ta 40 C
)
in places where emergency luminaires are
needed. The luminaires
GR-270 and GR-
272 are suitable for corridors lighting and
the
GR-271 and GR-273 for open area
lighting
.
Each device must be permanently
connected to mains power supply
.
In
normal operation the battery is charging. In
case of a mains power supply failure the
device will light the illumination led
automatically in emergency mode. When
the mains power supply is restored the
device turns to normal operation.
INSTALLATION
To install the luminaire follow the
installation instructions
ο
n page 2.
ΑΤΤΕΝΤΙΟΝ
!!!
1. Operations for installation, maintainance
or testing must be done by authorized
personel only
.
2.
The device must be connected to the
mains power supply thru a fuse dependent
by the total amount of the line’s power
load
.
3.
It is sugested to check every month the
indication LED for battery charging, and by
pushing the TEST button (use a pointy tool
with diameter of 2mm max.) to check the
emergency cirquit. The illumination LED
should light as long as the TEST button is
pressed
. In the opposite condition contact
the installer.
4.
It is sugested to check every 6 months
the minimum autononous duration by
disconnecting the mains power supply
.
Count the time that the luminaire lights and
in case of less time than the minimum
autonomous duration the battery must be
r e p l a c e d . I f t h e m e a s u r e d t i m e i s
considerably less than the minimum
autonomous duration
contact the installer.
I n c a s e o f b a t t e r y o r l i g h t s o u r c e
replacement, these must be replaced by
parts of the same type, by the manufacturer
or by a competent person.
5.
In case of inactive use for a period
greater than 2 months, disconnect the
b a t t e r y b y p u l l i n g o u t t h e b a t t e r y ’s
connector.
6.
I s not allowed to discard batteries in
t i
to common trash bins, they must be
discarded only
in battery recycling
points. Do not incinerate.
NON MAINTAINED SPOT LIGHT EMERGENCY
LUMINAIRES WITH 1 WHITE POWER LED
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIAL
EXTERNAL DIMENSION
WEIGHT
GUARANTEE
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERY (Ni-MH)
CHARGE TIME
INDICATIONS - CONTROLS
BATTERY PROTECTION
MINIMUM DURATION
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
EMERGENCY ILLUMINATION
LIGHT SOURCE
220-240V AC / 50-60Hz
3 hours
1.5 hour
24 hours
Deep discharge and overcharge protection
IP40
3.6V/1.5Ah
160lm
120lm
1 white
power LED
o
5 to 40 C
Up to 95%
ABS/PC, PC
3 years
(1
year for the battery
)
380gr.
Ø125 x 65 mm
EN 60598-1, EN 60598-2-22
, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
Charge
,
TEST button
GR-27
0
GR-271
GR-272
GR-273
2.4W / 2.7VA
TECHNICAL CHARACTERISTICS