background image

Page

 2

 from

 

4

The  light  source  contained  in  this  luminaire  shall  only  be  replaced  by  the 
manufacturer, or his agent, or a similar qualified person.

NOTE! The light source is non-user replaceable.

INSTALLATION INSTRUCTIONS

3

2

Initial installation

1

   

Untighten the screw and pull up the reflector.

2   

Always use in any case round mains cable

,

 with a diameter

 

of 5

-

10mm (H05RN-F type 2x1mm² 

or 

any 

other type

,

 

at least 

equal 

to it’s mechanical and electrical properties). ATTENTION!! 

The cable must not be deformed in any way (This requirement is important to ensure the 

ΙΡ 

rating). 

Install

 

the included gaskets in to the cable entry holes 

(verify that are not deformed)

. Make a 

hole in the center by using a small screwdriver. Pass the round cable through the gasket. Detach the 
power terminal, connect the wires as shown in the picture and attach the power terminal 

(10A max)

3

  

 Place the battery’s connector to the corresponding connector on the P.C.B.

4

  

 Refit the reflector (mind the correct orientation), tighten the screw securely and the luminaire 

     is ready for mounting

.

  

 
 

 

 

NOTE!!   After finishing the installation you must power the luminaire for, at least, 24 hours for 
battery charging to perform the nominal autonomy.

 GR-27

0

, GR-272

 GR-271, GR-273

ATTENTION!!! 
During installation follow this light direction. 

Corridor

lighting

Open 

area

lighting

CHARGE

TEST

CHARGE

TEST

CHARGE

TEST

9

6

6

5

125

CHARGE

TEST

Battery 
charge
indication 
LED

Figure 4

Test 
button

923270000_09_00

4

L

N

Cable 
entry
hole

1