background image

Page

 1

 from

 6

92329300

4

_09_00

4

GENERAL

o

This  device  is  used  indoors 

(

ta  40 C

)

  in 

places  where  emergency  luminaires  are 
needed.  Each  device  must  be  permanently 
connected  to  mains  power  supply

.

  The 

l u m i n a i r e s   G R - 2 9 0 / W P / M   a n d   G R -
292/WP/M  are  suitable  for  corridors  lighting 
and  the  GR-291/WP/M  and  GR-293/WP/M 
for  open  area  lighting.  In  normal  operation 
the  battery  is  charging.  In  case    of  a  mains 
power  supply  failure,  the  device  enters 
emergency  mode  and  the  illumination  LED 
turns on. When the  mains  power  supply is 
r e s t o r e d   t h e   d e v i c e   t u r n s   t o   n o r m a l  
operation.

INSTALLATION

To install the luminaire follow the installation 
instructions 

ο

n page 3.

Battery Charging

The 

battery 

charging 

is 

completely 

controlled

In  this  case,  is

 

achieved  the 

perfect  battery maintenance 

as well as the 

elongation  of  its  duration

When  the  battery 

has  completely  charged

it  charges  with  a 

maintenance current.

Battery Cut-off

The  device  in  this  operation  when  the  mains 
power  supply  fails

 

and  battery  has  lost  its 

energy

During  this  operation  the  device 

enters the idle state

 

and battery consumption 

is  negligible,  in  order  to  be  protected  from 
deep discharge.
 

Automatic Operational Test

It is conducted automatically every 15 days. In 
order  to  be  performed,  the  mains  power 
supply and the battery should be connected.

Automatic Autonomous Test

The Automatic Autonomous Test is conducted 
and measures the device’s back up operation 
and  emergency  duration.  The  BATTERY 
FAULT  LED  blinks  during    the  measurement, 
indicating this process to the user. This test is 
conducted  automatically  every  six  months

In 

order  to  be  performed,  the  mains  power 
supply  and  the  battery  should  be  connected 
and  fully  charged

If  the  battery  is  not  fully 

charged

the  test  is  postponed

 

until  the 

battery  is    completely  charged.  If  during  this 
test,  the  autonomy  is  less  than  the  nominal 
then  the  battery  fault  led  turned  on 
continuously  and  the  battery  must  be 

WATERPROOF

 

SELF TESTING N

ON

-M

AINTAINED

 EMERGENCY CEILING MOUNTED 

LUMINAIRE

S

OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERY (NiMh)

220-240V AC / 50-60Hz

4.8V/1.2Ah

4.3W / 4.7 VA

TECHNICAL CHARACTERISTICS

 

(for LED MODULE specifications see page 5)

Thank you for your trust in our products  

Olympia Electronics - European manufacturer

OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIAL
EXTERNAL DIMENSION
WEIGHT
GUARANTEE

CHARGE TIME

INDICATIONS - CONTROLS

BATTERY PROTECTION

MINIMUM DURATION

DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH

EMERGENCY ILLUMINATION

LIGHT SOURCE

1

.5

 hour

24 hours

Deep discharge and overcharge protection

IP

65

  300lm 

  1 white

 

power LED

o

5 to 40  C

Up to 95% 

ABS/PC

3 years

 (1 

year for the battery

)

442gr.

Ø125 x 6

5

 mm

EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3

Charge, lamp fault, battery fault

3 hours

  150lm 

 GR-29

0

/WP/M GR-291/WP/M GR-292/WP/M GR-293/WP/M

INSULATION BETWEEN SUPPLY & CONTROL TERMINALS

Basic insulation

Reviews: