Thank you for purchasing this product of
O l y m p i a E l e c t r o n i c s . A E u r o p e a n
manufacturer.
GENERAL
These luminaires are suitable for marine and
offshore applications where emergency light
i s n e e d e d . E a c h l u m i n a i r e m u s t b e
permanently connected to mains power
supply. In normal operation the led strip lights
and the battery is charging. In case of a
mains power supply failure the luminaire will
light the led strip automatically in emergency
mode. When the mains power supply is
restored the device turns to normal operation.
INSTALLATION
To install the luminaire follow the installation
instructions on page 4.
Battery Charging
The battery charging is completely controled.
In this case, is achieved the perfect battery
maintenance , as well as the elongation of its
duration. When the battery has completely
charged, it charges with a maintenance
current.
Battery Cut-off
The luminaire enters in this operation when
the mains power supply fails and battery has
lost its energy. During this operation the
luminaire enters the idle state and battery
consumption is negligible, in order to be
protected from deep discharge.
Manual Test
The manual test can be conducted only if the
main power supply and the battery is
connected. By pressing the test button briefly
an operation test is initiated. During this test
period all indication LEDs are OFF.
Automatic Test
This test includes all the operations that
provide the manual test and is conducted
automatically every 15 days. In order to be
performed, the main power supply and the
battery should be connected.
Automatic Autonomous Test
The Automatic Autonomous Test is conducted
and measures the luminaire`s back up
operation. This test is conducted automatically
every six months. In order to be performed,
the main power supply and the battery should
be connected (the battery should be charged).
If the battery is not charged, the test is
postponed until the battery is completely
charged. If during the Automatic Autonomous
Test the luminaire’s duration is lower than the
nominal, then the battery must be replaced.
Back Up Operation
The autonomous duration of battery during
emergency mode is at least the one that is
923423012_09_002
Page 1 from 4
SELF TESTING MAINTAINED EMERGENCY LUMINAIRES
220-240V AC/50-60Hz
3W / 6.5VA
4W / 7VA
Bayblend FR3010, transparent polycarbonate
TECHNICAL CHARACTERISTICS
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
EXTERNAL DIMENSIONS
CONSTRUCTION MATERIALS
TYPICAL WEIGHT
GUARANTEE
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERIES (Ni-Cd)
CHARGING TIME
INDICATIONS - CONTROLS
BATTERY PROTECTION
MINIMUM AUTONOMOUS DURATION
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
ILLUMINATION (230V / EMERGENCY)
ILLUMINATION SOURCE
180min
24h
Charge, lamp fault, fault indication LED, TEST button
From overcharge and full discharge
IP 42
3.6V/1Ah
85/85lm
170/170lm
12 white LED’s
24 white LED’s
5 to 40 C
o
Up to 95%
3 years (1 year for the battery)
480gr.
272 x 121 x 50 mm
GR-423/12L/MAR
GR-423/24L/MAR
3.6V/2Ah(NiMH)
560gr.
High Quality European based Manufacturers
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3, IEC 60092-306, IEC 60533