Back Up Operation

The  autonomous  duration  of  battery  during 
emergency  mode  is  at  least  the  one  that  is 
stated 

in 

the 

list 

of 

the 

technical 

characteristics.  During  emergency  mode,  a 
light source test is also performed.

Resetting Errors 

Place the test card A-1900  on the side of the 
indications  (page  4)  and  remove  it  after  the 
reset  is  conducted  (the  indications  light  in 
sequence),  to  delete  all  the  indicated  LED 
errors.  Then  the  luminaire  enters  regular

 

operation mode.

Indication  LED  status  (with  connected 
mains power supply).

Charge 

On:

 

Good charge current.

Οff:

 

No battery 

(

No charging current 

or disconnected battery

).

Lamp Fault 

(with L1 connected to L)

Οn

 

(with  LED  strip  off)

:

 

Faulty  LED  strip 

(must be replaced).

Οn

 (with LED strip on)

:

 

Problem in the back 

up  circuit  of  the  LED  strip  (must  be  checked 
by an authorized personnel).

Off:

 

 Good LED strip.

Battery Fault

 

Ο

ff

:

 

Battery OK. 

Blink

  (

With  Charge  LED  ON):

  Autonomy  or 

low  battery  problem 

(the  battery  must  be 

replaced).

Blink

 

(

With  Charge  LED  Off): 

No  charging 

current or disconnected battery

.

 

ΑΤΤΕΝΤΙΟΝ!

!!

1.  Operations  for  installation,  maintainance 
or  testing  must  be  done  by  authorized 
personnel only, after a mains interruption

.

2.  The  device  must  be  connected  to  the 
m a i n s   p o w e r   s u p p l y   t h r

o

u

g h

  a   f u s e  

dependent  on  the  total  amount  of  the  line’s   
power load.

3. 

In  case  of  battery  or  lamp  replacement, 

these must be replaced by parts of the same 
type, by the manufacturer or by a competent 
person.

                

4. In case of inactive use for a period greater 
than  2  months,  disconnect  the  battery  by 
pulling out the battery’s connector. 
5

I

s  not  allowed  to  discard  batteries 

t  i

into  common  trash  bins,  they  must 
b e   d i s c a r d e d   o n l y  

i n   b a t t e r y  

recycling points. Do not incinerate.

INSTALLATION

To install the luminaire follow the installation 
instructions on page 3.

923

577

00

7

_09_0

01

The light source contained in this luminaire shall only be replaced by the manufacturer, or his 

agent, or a similar qualified person.

NOTE! The light source is non-user replaceable.

(*) 

Maintained operation:

 The luminaire lights its illumination source, when it is powered by the 

mains power supply or not

.  

 

Non Maintained operation: The luminaire lights its illumination source, only in  power supply’s 
failure.

NOTE: 

LED= Light Emitting Diode

LABELING EXPLANATION:
X: 

Self contained 

  

1:  

Maintained (*)

A: 

Including test device

G: 

Internally illuminated 

 

90: 

1.5 hour duration 

18

0: 

3

 hour duration 