Webserver:

In order to set up the parameters for Gateway - PC Software communication, enter the webserver.
To enter webserver interface, first power on the device, connect the device to the Ethernet network
(RJ45  connector)  and  then  enter  the  default  IP  to  a  common  Web  Browser  via  PC 
(Chrome/Firefox/etc). 

In  order  to  have  access  to  the  Gateway,  the  IPv4  address  range  must  be  from  10.0.1.2  to 
10.0.1.254, except 10.0.1.142 which is already occupied by the Gateway. 

Webserver main screen interface:

In order to set up the master IP, of the PC that runs the GR-7600 PC Software enter 

“TECHNICIAN 

MENU” 

from the left tab, enter technician code (default: 1000) and then enter 

“MASTER IP” 

menu.

Enter the static IP of the PC (3 digit numbers, fill with zeros where needed)
Enter the MAC address of the PC’s Ethernet adaptor (see details in Local Area Network connection 
status, Physical address line).

Press 

“SAVE” 

to save configurations to the Gateway. The Gateway will now send and receive all the 

data regarding the wireless emergency illumination network, to/from this IP.

Via 

“CHANGE TECH CODE” 

option you can change the default technician password from 1000 to 

another 4 digit number, in order to block access from unwanted sources.
Always enter a 4 digit number. Changing the tech code is an action that should be done responsibly, 
as there is no way to restore the default tech code without losing any saved other configurations.