Οδηγίες Εγκατάστασης
3
Installation Instructions
Lens Installation
Anti-Panic
Escape Route
923796000
_0
9
_001
923796000
_0
9
_001
2
1
Dimensions
3
130mm
Dip Switch Positions (DS1)
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
1h
(default position)
3h
8h
Install the 2 springs contained in the package to the bottom cover of the luminaire. Install
them as shown in the Figure.
Place a flat blade screwdriver on the
5
marked positions and swift it, pull up gently the
bottom cover and remove it.
The user can select one of the 3 available minimum autonomy
durations: 1 hour, 3 hours and 8 hours. The selection must be
done while the luminaire is disconnected from AC and battery
supplies. The selection is achieved through Switches 2 & 3 of
DS1. Switches 1 and 4 are not used.
Two additional labels are included in the package, one for 3 hours duration (180) and one for
8 hour duration (480). Depending on the selected duration, the installer must cover the
default 1 hour (60) printing with one label that has the required duration. Please take notice
of the orientation of the label.
6.3mm
Ceiling opening
121mm
118mm
30mm
Figure
1
1
2
1
1
Luminaire
Manual
Labels for 3 & 8 hours duration
Lens Accessories
Set of Mounting Springs
General
Package Contents
Indications
Indications
LED Status
Description
GREEN
(charge)
Normal
Charging
(battery test not possible whilte charging)
Mains off
(battery not connected or charger fault)
Light Source Test (Duration: 3s)
Light Source Fault
Battery Test (Duration: 1h, 3h, 8h)
Battery Fault
Battery Fault & Light Source Fault
RED
(Batt./Lamp
Fault)
Note:
Permanently
ON
Fast Blink
Slow Blink
Off
Red LED
(Battery/Lamp Fault)
Green LED
(
Charge)
In order to place the proper lens (Anti - Panic or Escape Route), first be sure that the luminaire is
not connected in the mains power supply and the battery is disconnected. Place the proper lens
and retaining cover on the luminaire.
Be careful not touch the LED with your hand.
In order to change the lens, be sure that the luminaire is not connected to the mains power
supply and the battery is disconnected. Use a flat bladed screwdriver to remove the retaining
cover, remove the placed lens and insert the new one with its retaining cover.
Be careful not to touch the LED with your hand.
o
These devices are used indoors
(
ta 40 C
)
in places
where emergency light is needed. Each device must
be permanently connected to mains power supply
.
In normal operation the battery is charging. In case
of a mains power supply failure, the device enters
emergency mode and the illumination LED turns on.
When the mains power supply is restored the
device turns to normal operation.
Automatic Operational Test
Automatic Autonomy Test
T
his test is conducted automatically every 15 days
and lasts 3 seconds. The light source and the
emergency circuit of the device are tested. The test
can be conducted only if the mains power supply
and the battery are connected. During this test
period the light source will light up and the green
LED will flash quickly. The battery must have
adequate charge.
The Automatic Autonomy Test is conducted every 6
months and measures the device’s back up
operation and emergency duration. In order to be
performed, the mains power supply
should be
connected and the battery should be fully charged.
During this test period the light source will light up
and the green LED will flash quickly. This test lasts for
the stated duration. In case the test shows a battery
fault, then the battery needs to be replaced. After
the replacement, the luminaire will charge the
battery. When the charge is finished, the luminaire
will perform an automatic autonomy test which lasts
for the stated duration. If the battery is in good
condition then the LED indicator will turn off.
Addressable Communication
T
he luminaire has the ability to be connected to the
Olympia Electronics addressable panels. In order to
do so, the luminaire’s address has to be unique in
the same bus. For the different address dip switch
settings, see the extra leaflet.
ΑΤΤΕΝΤΙΟΝ!
!!
3. The device must be connected to the mains
power supply through a circuit breaker that is
depends on the total line’s power load.
5. In case of inactive use for a period greater than 2
months, disconnect the battery by pulling out the
battery’s connector.
1. Operations for installation, maintainance or
testing must be done by authorized personnel
only
.
2. Always use in any case round mains cable
,
with a
diameter
of 5
-
10mm (H05RN-F type 2x1mm²
or
any
other type
,
at least
equal
to it’s mechanical
and electrical properties). ATTENTION!! The cable
must not be deformed in any way (This
requirement is important to ensure the
ΙΡ
rating).
4. In case of battery replacement, it must be
replaced by the same type, by the manufacturer
or a competent person.
6.
I
s not allowed to discard batteries into
t i
common trash bins, they must be discarded
only
in battery recycling points. Do not
incinerate.
4
Pass the mains cable through the hole and connect
them to the terminal blocks. L for live wire N for
neutral. The ground terminal is for termination
purposes only. To connect the luminaire with the
addressable panel, pass the 2 signal cables and
connect them on the C1 and C2 terminals, minding
the correct polarity. Set the luminaire address via
the dip switch. For the different address dip switch
settings, see the extra leaflet.
Power & Communication Connections
N
for Neutral,
L
for Live wire
Dip Switch Settings
N
L
B-C2
A-C1
N
L
PE
C1
C2
From the
Panel