Thank you for purchasing this product of Olympia
Electronics. A European manufacturer.
GENERAL
These luminaires are used in places where
e m e r g e n c y l u m i n a i r e s a r e n e e d e d . E a c h
luminaire must be permanently connected to
mains power supply
.
In normal operation the led
strip lights and the battery is charging. In case of
a mains power supply failure the luminaire will
light the led strip automatically in emergency
mode. When the mains power supply is
restored the device turns to normal operation.
INSTALLATION
To install the luminaire follow the installation
instructions on page 2.
OPERATION
Battery Cut-off
The luminaire enters in this operation when the
mains power supply fails
and battery has lost its
energy
.
During this operation the luminaire enters
the idle state
and battery consumption is
negligible, in order to be protected from deep
discharge.
Battery charging
The battery charging is completely controlled
.
In
this case, is
achieved the perfect battery
maintenance
,
as well as the elongation of its
duration
.
When the battery has completely
charged
,
it charges with a maintenance current.
Manual
Test
The manual test can be conducted only if the
main power supply and the battery is connected.
By pressing the TEST/RESET button briefly (page
2) an operation test is initiated. During this test
period all indication LEDs are OFF.
Automatic test
This test includes all the operations that provide
the manual test and is conducted automatically
every 15 days. In order to be performed, the main
power supply and the battery should be connected.
Automatic Autonomous Test
The Automatic Autonomous Test is conducted and
measures the luminaire`s back up operation. This
test is conducted automatically every six months
.
In order to be performed, the main power supply
and the battery should be connected (the battery
should be charged)
.
If the battery is not charged
,
the test is postponed
until the battery is completely
charged. If during the Automatic Autonomous Test
the luminaire’s duration is lower than the named,
then the battery must be replaced.
Back Up Operation
The autonomous duration of battery during
emergency mode is at least the one that is stated
in the technical characteristics. During emergency
mode, a LED strip test is also performed.
Resetting Errors
Push the TEST/RESET button for 5 seconds, to
extinguish all the indicated LED errors (page 2).
Then the luminaire enters regular
operation mode.
Indication LED status
(with connected mains power supply).
Charge
On:
Good charge current.
Οff:
No battery
(
No charging current or
disconnected battery
).
Lamp fault
Οn:
faulty LED strip.
Off:
Good LED strip.
Fault
Ο
ff
:
Battery OK.
WATERPROOF SELF-TESTING EMERGENCY LUMINAIRES
Page
1
from
2
220-240V AC/50-60Hz
5W / 8.5VA
Bayblend FR3010
,
transparent
polycarbonate
TECHNICAL CHARACTERISTICS
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
EXTERNAL DIMENSIONS
CONSTRUCTION MATERIALS
TYPICAL WEIGHT
GUARANTEE
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERY
(
Ni-Cd
)
CHARGING TIME
INDICATIONS
BATTERY PROTECTION
MINIMUM AUTONOMOUS DURATION
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
ILLUMINATION (MAINS / EMERGENCY)
ILLUMINATION SOURCE
90min
24h
Charge, lamp fault, fault indication LED
From overcharge and full discharge
IP 65
3.6V/3Ah
210lm / 210lm
30 white LED’s
EN 60598-1, EN 60598-2-22
, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
0 to 40 C
o
Up to 95%
3 years
(1
year for the battery
)
920gr.
3
63
x 145 x 73 mm
3.5W / 7.5VA
3.6V/1Ah
105lm / 105lm
15 white LED’s
180min
5W /8.5VA
3.5W / 7.5VA
3.6V/1.5Ah
210lm / 210lm
105lm / 105lm
30 white LED’s
210lm / 210lm
15 white LED’s
GR-938/30L
GR-938/15L
GR-939/15L
GR-939/30L
790gr.