GENERAL
These luminaires are used in places where
emergency luminaires are needed. Each
luminaire must be permanently connected to
mains power supply
.
In normal operation (L1
connected to L) the led strip lights and the
battery is charging. In case of a mains
power supply failure the luminaire will light
the led strip automatically in emergency mode
(powered by its battery). When the mains
power supply is restored the device turns to
normal operation.
INSTALLATION
To install the luminaire follow the installation
instructions on page 3.
OPERATION
Battery Charging
The battery charging is completely controlled
.
Thereby,
the
best
possible
battery
maintenance is
achieved
,
as well as the
elongation of its duration
.
When the battery
has completely charged
,
it charges with a
maintenance current.
Battery Cut-off
The luminaire enters in this operation when
the mains power supply fails
and battery has
lost its energy
.
During this operation the
luminaire enters the idle state
and battery
consumption is negligible, in order to be
protected from deep discharge.
Manual
Test
The manual test can be conducted only if the
mains power supply and the battery is
connected. By pressing the TEST/RESET
button briefly (page 3) an operation test is
initiated. During this test period all indication
LEDs are OFF.
Tests
Normally the illumination source and the
autonomy tests are programmed by the
control panel and the test results are sent to
the control panel.
Automatic Operational Test
This test includes all the operations that
provide the manual test and is conducted
automatically every 15 days. In order to be
performed, the mains power supply and the
battery should be connected.
Automatic Autonomous Test
The Automatic Autonomous Test is conducted
and measures the device’s back up operation
220-240V AC/50-60Hz
4.5W / 4.9VA
ABS/PC, PC
TECHNICAL CHARACTERISTICS
(for LED MODULE Specs. see page 4)
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
EXTERNAL DIMENSIONS
CONSTRUCTION MATERIALS
TYPICAL WEIGHT
GUARANTEE
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERIES
(
Ni-Cd
)
CHARGING TIME
INDICATIONS
BATTERY PROTECTION
MINIMUM AUTONOMOUS DURATION
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
ILLUMINATION (MAINS / EMERGENCY)
ILLUMINATION SOURCE
90min
24h
Charge, Lamp Fault, Battery Fault indication LED
From overcharge and deep discharge
IP 65
3.6V/3Ah
210lm / 210lm
30 white LEDs
EN 60598-1, EN 60598-2-22
, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
5 to 40 C
o
Up to 95%
3 years
(1
year for the battery
)
930gr.
3
63
x 145 x 73 mm
3.4W / 3.8VA
GR-938/15L
GR-938/30L
GR-939/15L
GR-939/30L
3.6V/
0.6
Ah
105lm / 105lm
15 white LEDs
180min
5.3W /5.6VA
3.3W / 3.7VA
3.6V/1.5Ah
210lm / 210lm
105lm / 105lm
30 white LEDs
15 white LEDs
790gr.
860gr.
Thank you for your trust in our products.
Olympia Electronics - European manufacturer
.
WATERPROOF SELF TESTING MAINTAINED EMERGENCY LUMINAIRES