 1

 from

 

5

923939013_09_004

+20gr 

ΤΟ 

ADDRESS MODULE

GENERAL

These luminaires are used in places where 
emergency luminaires are needed. Each 
luminaire must be permanently connected to 
mains power supply.

 

In normal operation (L1 

connected to L) the led strip lights and the battery 
is charging.

 

In case of a mains power supply 

failure the luminaire will light the led strip 
automatically in emergency mode (powered by its 
battery). When the mains power  supply is 
restored the device turns to normal operation. 

Address Operation

The luminaires can be connected to a GR-6500 
address  panel.  For  address  operations  refer  to 
the installation manual of the panel. 
For address module connections see page 3. 
For dip-switch addressing selection see page 4, 5 
and 6.

INSTALLATION

To  install  the  luminaire  follow  the  installation 
instructions on page 3.

Battery Charging

The battery charging is completely controlled

In 

this case, the best possible  battery maintenance 
is

 

achieved

as  well  as  the  elongation  of  its 

duration

When  the  battery  has  completely 

charged

it charges with a maintenance current.

Battery Cut-off

The  luminaire  enters  in  this  operation  when  the 
mains  power  supply  fails

 

and  battery  has  lost  its 

energy

During this operation the luminaire enters 

the  idle  state

 

and  battery  consumption  is 

negligible,  in  order  to  be  protected  from  deep 
discharge.

Manual

 Test

This  test  can  be  done  by  pressing  the 
TEST/RESET  button  briefly  (page  3).  The  light 
source and the emergency circuit of the device is 
monitored. The manual test can be conducted only 
if  the  mains  power  supply  and  the  battery  is 
connected.  During  this  test  period  all  indication 
LEDs are OFF. 

Tests

Normally the illumination source and the autonomy 
tests are programmed by the control panel and the 
test results are sent to the control panel.

If  the  luminaire  is  not  connected  to  GR-6500 
panel, the following automatic tests executed:

Automatic operational test

This  test  includes  all  the  operations  that  provide 
the  manual  test  and  is  conducted  automatically 
every 15 days. In order to be performed, the mains 
power  supply  and  the  battery  should  be 
connected. 

Automatic Autonomous Test

The Automatic Autonomous Test is conducted and 

                         ADDRESSABLE WATERPROOF SELF TESTING MAINTAINED EMERGENCY LUMINAIRES WITH WHITE LEDs

 GR-938/4P/ADR  GR-939/4P/ADR  GR-938/6P/ADR  GR-939/6P/ADR

OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY

EXTERNAL DIMENSIONS 

CONSTRUCTION MATERIALS 

TYPICAL WEIGHT
GUARANTEE 

OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERIES (Ni-Cd)

CHARGING TIME

INDICATIONS

BATTERY PROTECTION

MINIMUM AUTONOMOUS DURATION

DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH

ILLUMINATION (MAINS / EMERGENCY)

ILLUMINATION SOURCE 

Thank you for your trust in our products  

Olympia Electronics -  European manufacturer

TECHNICAL CHARACTERISTICS

 

(for LED MODULE Specifications see page  )

5

220-240V AC/50-60Hz

5.9W/8.4VA

5W/7.7VA

6W/8.5VA

4W/7.5VA

Bayblend FR3010

transparent 

 

polycarbonate

180min

180min

90min

90min

24h

Charge, lamp fault, fault indication LED

From overcharge and deep discharge

IP65

4.8V/1.5Ah

4.8

V/4Ah(Ni-MH)

4.8

V/

3

Ah

  175/350lm 

  245/480lm 

  4 white power LEDs 

  6 white power LEDs 

o

5 to 40  C

Up to 95% 

3 years 

(1 

year for the battery

)

940gr.

1030gr.

1080gr.

363 x 145 x 73 mm 

EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3

Reviews: