background image

Page

 1 

from

 

4

923038000_09_001

SELF TESTING NON MAINTAINED EMERGENCY LUMINAIRES

TECHNICAL CHARACTERISTICS

 (

for LED MODULE Specifications see page 

4

)

220-240V AC/50-60Hz

90 min.

<24 h

POWER

-

CHARGE indicator, LAMP

 

FAULT

BATT

FAULT indicator, TEST button

From overcharge and deep discharge

IP42

2x12V/7Ah

  White Power

 

LEDs

13

.

3W/

14

VA

EN 60598-1, EN 60598-2-22

, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3

5 to 40  C

o

Up to 95% 

Aluminum, ABS/PC, PC

3 years 

(1 

year for the battery

)

  3000lm 

3

02

 

x 94 x 

3

50 mm.

6358gr.

Thank you for your trust in our products  

Olympia Electronics -  European manufacturer

GRL-38/180/M

OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY

EXTERNAL DIMENSIONS 

CONSTRUCTION MATERIALS 

TYPICAL WEIGHT

GUARANTEE 

OPERATION VOLTAGE

MAXIMUM POWER CONSUMPTION
BATTERIES

 (

Pb

)

CHARGING TIME

INDICATIONS 

CONTROLS

BATTERY PROTECTION

MINIMUM AUTONOMOUS DURATION

DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH

EMERGENCY ILLUMINATION

LIGHT SOURCE

12V/7Ah

180 min.

4182gr.

GRL-38/90/M

GENERAL

o

These luminaires are used 

(

ta 40 C

)

 where 

emergency light is needed.

 

Each luminaire 

must  be  connected  permanently  to  the 
mains power supply.

 

OPERATION DESCRIPTION

 

When the unit is connected to the mains power 
supply

  (

after  connecting  the  battery

the 

indicator LAMP

 

FAULT

 – 

BATT

FAULT

 

remains 

OFF whereas the indicator

 

POWER

 

CHARGE

 

blinks to indicate that the batteries are charging

When  the  batteries  are  fully  charged  this 
indicator will light permanently.

 

If this indicator 

does not light then probably the battery has not 
been connected.

 

If the batteries are connected 

and the indicator does not light then contact a 
qualified service technician for assistance.

 

The 

charging  procedure  is  monitored  by  a 
microprocessor and is based on a 3 stage cycle 
thus  ensuring  a  fast  and  full  charge  of  the 
battery.

 

The charge current is supplied by a high 

efficiency  switch  mode  power  supply  which 
ensures  perfect  charging  even  during  the 
fluctuations of the mains power supply.

BATTERY CUTOFF

The  unit  enters  this  state  during  the  power 
supply failure and when the battery has been 

fully discharged. In this state the luminaire draws 
the  least  power  from  the  battery  in  order  to 
prevent 
deep discharge.

MANUAL TESTING

Is accomplished by briefly (<1 sec.) pressing the 
TEST button. This permits   the user to test the 
good  operation  of  the  luminaire’s  emergency 
circuit.

 

The unit simulates a power failure and the 

lamps are lit using the batteries. This manual test 
does not affect the automatic test

.

DIMMING OPTION

When the 

luminaire is in emergency mode

, with 

corresponding press

ing

s of the button, we ca

n

 

choose 

the illumination of 100%, 50%, 33% 

 or 

turned off

, either to increase the autonomy time 

or  not  to  consume 

the 

battery  power 

unnecessarily. This option is canceled when the 
network is restored.

LAMP TESTING

The  luminaire  tests  the  good  condition  of  the 
lamps in emergency mode and warns the user 
for probable malfunction. If a lamp is found faulty 
then the LAMP FAULT indicator starts to blink. To 
verify which lamp is faulty use the TEST button. If 

Reviews: