                         MAINTAINED/NON-MAINTAINED (OPTIONAL) ILLUMINATION SIGNS WITH WHITE LEDs

GENERAL

These  sign  illumination  luminaires  use  a  new 
technology,  friendly  to  the  environment,  with  high   
illuminated  L.E.D.s.  L.E.D.  technology  has  very  low   
power  consumption. 
The  edge  illumination  sign  is  used    as  a  maintained 
emergency lighting with  indications  symbols. 
In  this  type  of  marking  panels,  the  PVC  overlay  is 
mounted  on  the  marking  panel  with  4  plastic  screws, 
and  it  can  be  changed  by  change  the  PVC  overlay  in 
accordance with the desired result.   
Each  model  combines  modern,  aesthetics,  together   
with    functionality.  The  exit  illumination  signs  are  used 
in  every  public  area  where  clear  direction  and  good   
appearance are important.

NON MAINTAINED OPERATION

By default the illumination sign operates as maintained. 
The  device  has  a  possibility  to  operate  as  non 
maintained.  To  change  the  maintained  to  non-
maintained operation follow the relative instructions on 
page 6.
All  models  must  be  permanently  connected  to  the   
mains power supply as shown on page 2.
The  legend  is  screened  on  to  a  clear  acrylic  sheet 
which  has  the  marking  on  the  marking  panel  with  the 
light  that  comes  from  the  top  of  the  luminaire  and 
diffracts, giving light to the marking panel. 
The  luminaire  has  an  indication  (CHARGE)  for  the 
charging  of  the  battery  and  a  (TEST)  button  to  TEST   
the emergency circuit and the LEDs for good  operation 
only when the luminaire is powered by the mains power 
supply.  The  unit  must  be  mounted  in  a  clearly  visible 
area and can either be hung on a ceiling or mounted on 
a  wall  depending  on  the  requirements  of  the 
installation.  The  package    includes  all  the  required 
materials  for  mounting  on    the  wall  or  on  the  ceiling. 
The  pages  2,3  and  4  show    us    the    mounting   

methods.  

WARNING !!

1. Read carefully this instruction manual.
2. Before service interrupt the mains power supply.
3.  The  device  must  be  connected  to  the  mains  power 
supply through a fuse dependent by the total amount of 
the line’s  power load.
4.  It  is  suggested  to  check  every  month  the  indication 
LED  for  battery  charging,  and  by  pushing  briefly  the 
TEST  button  to  check  the  emergency  circuit. The  sign 
should  light  for  a  few  seconds  powered  by  the  battery 
and then, will turn to normal operation

5. 

full 

by  disconnecting  the  mains  power  supply

Count the autonomous duration of the luminaire and in 
case  of  no  correspondence  to  stated  emergency 
duration  replace  the  battery The  replacement  of  the 
battery must be done using parts of the same type, by 
the manufacturer or by a competent person.

7

Replaced batteries must not be thrown into 

trash  bins.  They  must  be  returned  to  special 
battery disposal points.
Do not incinerate.

NOTE: LED= Light Emitting Diode

LABELING EXPLANATION:
X: 

Self contained 

     1: 

Maintained

 (*)

A: 

Including test device

   G: 

Internally illuminated 

safety sign.

    180: 

3 hour duration

(*) Maintained operation: The luminaire lights its 
illumination source, when it is powered by the mains 
power supply or not.
Non-Maintained operation: The luminaire lights its 
illumination source, only in  power supply’s failure. 

  

. In the opposite 

condition contact the installer. 

Every  six  months,  a 

duration  check  should  be 

carried  out 

 

6.  In  case  of  inactive  use  for  a  period  greater  than  2 
months,  disconnect  the  battery  by  pulling  out  the 
battery’s connector.

922504417_09_032

Page 1 from 6

 MLD-34D/w

MLD-44D/w

 MLD-28D/w

TECHNICAL CHARACTERISTICS

FOR LED MODULE SPECS. see page 6

Operation  temperature range

Relative humidity
External panel's dimensions
External dimensions (LxWxH)

Typical weight

Guarantee

Mains voltage

Maximum power consumption
Battery (Ni-Cd)

Recharging  time

Battery protection

Minimum emergency duration

Degrees of cover protection
Class of cover protection
Produced in accordance with 

Light source intensity (Mains / Emerg)

220-240V AC/50-60Hz

3h

24h

Overcharging and deep discharging protection

IP40

class 

II

3.6V/1Ah

105lm/85lm

  85lm/85lm 

3W / 8VA

3W / 7.5VA

5-40  C

ο

up to 95% 

280x100mm

305x25x155mm

3 years (1 year for the battery)

340x170mm

365x25x225mm

440x220mm

465x25x275mm

EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3

520gr.

850gr.

1310gr.

Thank you for your trust in our products.  Olympia Electronics - European manufacturer.

Construction material

ABS/PC, Acrylic plate, PVC