Page 6 from 6
MAINTAINED TO NON MAINTAINED SELECTION CAPABILITY
Power on the device and press continuously the TEST button for 5 seconds, until the led strip
turns off. Release the button and after a short emergency test, the device operates as
non maintained. If you want to restore the previous condition (maintained operation), press
continuously the TEST button for 5 seconds, until the led strip lights. Release the button and
after a short emergency test, the device operates as maintained illumination sign.
Troubleshooting
Trouble
1. The illumination sign does not light when the TEST
button is pressed.
2. During the 6month autonomous check, t
illumination sign does not light or has less autonomy
than the nominal.
he
3.
operation.
The illumination sign does not light in normal
4.
failure
The illumination sign does not light during a mains
.
The battery has lost it’s energy
Wait at least for 1 hour for the battery to be charged.
Attach the battery’s connector to the appropriate
connector on the P.C.B.
The battery is inappropriate
Τhe battery must be replaced.
The battery is not connected
The battery has lost it’s energy
Wait at least for 24 hours for the battery to be fully
charged.
The battery is inappropriate
Τhe battery must be replaced.
The illumination sign is adjusted to operate as
non-maintained
Choose (if you must) to turn the operation to
maintained, according to relative paragraph in
page 6.
The battery has lost it’s energy
Wait at least for 24 hours for the battery to be fully
charged.
The battery is not connected
Attach the battery’s connector to the appropriate
connector on the P.C.B.
The battery is inappropriate
Τhe battery must be replaced.
Solution
922504417_09_032
MLD-34D/w
MLD-44D/w
MLD-28D/w
LED MODULE CHARACTERISTICS
Manufacturer
Model Number
Voltage Range
Connections
Nominal Power
Temperature (tc)
Olympia Electronics S.A.
45 °C max. across the board
fixed connection between main pcb and led module
8.5-10.5V DC
1802161
1702161
1902161
800mW
980mW
980mW
WARRANTY
Olympia Electronics guarantees the quality, condition and operation of the goods. The period of warranty
is specified in the official catalogue of Olympia Electronics and also in the technical leaflet, which
accompanies each product. This warranty ceases to exist if the buyer does not follow the technical
instructions included in official documents given by Olympia Electronics or if the buyer modifies the goods
provided or has any repairs or re-setting done by a third party, unless Olympia Electronics has fully
agreed to them in writing. Products that have been damaged can be returned to the premises of our
company for repair or replacement, as long as the warranty period is valid.
Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the
buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the
buyer the transportation cost.
HEAD OFFICE
72
nd
km. O.N.R. Thessaloniki-Katerini
P.C. 60300 P.O. Box 06 Εginio Pierias Greece
www.olympia-electronics.gr
info@olympia-electronics.gr