 BS- 634, BS- 636

 

Conventional 

Fire 

Alarm

 Panels

2, 4 and 6 zone 

921163600_09_020

Thank you for purchasing this product of Olympia Electronics. A European manufacturer.

GENERAL

The family of fire detection panels consist of 

3

 types (

2, 

4 and 6 zone) with identical operation and indications. The panels have 

2 independent siren outputs, Alarm, Fault Relay and a programmable AUX relay. The required batteries for the panels are two 
A-9

20

 (12V/

2.6

Ah). All functions and indications are according to European Norms EN 54-2 and EN 54-4.

Top cover 
retaining screws

Control Keyboard and 
indication leds

Mounting holes

Battery compartment 
two Α-920

 MODE selection 
    microswitch

Relay  

outputs 

connection  terminals

Zone connection terminal

General output connection 

(Sirens,24V)

Mains voltage connection 
terminal block (220-240V AC)

Figure 1. 

Schematic diagram of the panel

                

Mounting hole

Extra earth 
terminals

Page 1 from 

10

High Quality European based Manufacturers

Summary of Contents for nsc BS-1632

Page 1: ...e AUX relay The required batteries for the panels are two A 920 12V 2 6Ah All functions and indications are according to European Norms EN 54 2 and EN 54 4 Top cover retaining screws Control Keyboard...

Page 2: ...respond to the siren outputs If a siren out has a short circuit or open circuit then the corresponding LED will blink If a siren is disabled the corresponding LED will light The next group of indicato...

Page 3: ...siren 1 and Siren2 LED lights for the siren 2 Using the keys 1 and 2 we can enable or disable the respective sirens The disabled sirens have a LED lighted The panel exits this mode if no key is press...

Page 4: ...d corresponding functions 921163600_09_020 Fault zone 1 Alarm zone 2 Alarm zone 1 Without Delay 30 second Delay 60 second Delay 90 Second Delay LED ON LED OFF LED OFF LED OFF LED OFF LED OFF LED ON LE...

Page 5: ...res with a cross section cable of 1 5mm Page 5 from 10 Figure 2 Connecting 4 detector bases to zone 1 Each base can accept BS 655 BS 660 or BS 657 detectors A remote indication LED BS 572 is connected...

Page 6: ...larm condition ATTENTION The relays are rated at 30VDC and 5A maximum No 230VAC signals can be connected to these relays Siren Sounder Connections Each panel offers 2 independent circuits for connecti...

Page 7: ...out by qualified personnel only Disconnect power before servicing Never insert or remove boards or componets with the power on During installation use grounded antistatic wrist band to protect this e...

Page 8: ...ble LEDs blink If an alarm is manually given by either activating a BS 536 call point or by activating a smoke detector with smoke or simulated smoke particles the corresponding Alarm LED of the zone...

Page 9: ...s output must be protected with a fuse of the same rating contacts are rated at 30VDC and 5A maximum Outputs Relays 325 x 240 x 85 mm 54 2 54 4 2 years Dimensions Weight Produced in accordance to Guar...

Page 10: ...LINDROS PIERIAS 60061 GREECE BS 1632 14 0848 CONVENTIONAL 4 ZONE FIRE ALARM PANEL INSTALL IN ACCORDANCE WITH PRODUCT MANUAL 921163600_08_019 GREEK 921163600_09_020 ENGLISH POWER SUPPLY 220 240V AC 50...

Reviews: