background image

ATTENTION!!!

CAUTION : Do not view directly with bare eyes.

X 1

6 0

A F

G

OLY-1004/LT/WP

WATERPROOF SELF TESTING

MAINTAINED/NON MAINTAINED

EMERGENCY LUMINAIRE

IP65

923100410_09_003

923100410_09_003

4

5

X:

 Self contained

LABELING EXPLANATION:

A:

 Including test device

1:

 Maintained operation 

(*) 

NOTE:

 LED= Light Emitting Diode

F:

 Automatic test gear complying with IEC 61347-2-7 denoted EL-T

60:

 1 hour duration

180:

 3 hours duration

480:

 8 hours duration

G:

 Internally illuminated safety sign

(*)  Maintained  operation:  The  luminaire  lights  its  illumination  source,  when  it  is  powered  by  the 
mains power supply or not. 
Non Maintained operation: The luminaire lights its illumination source, only in mains power supply’s 
failure.

Warranty

Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the 
buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the 
buyer the transportation cost.

Olympia Electronics guarantees the quality, condition and operation of the goods. The period of warranty 
is  specified  in  the  official  catalogue  of  Olympia  Electronics  and  also  in  the  technical  leaflet,  which 
accompanies  each  product.  This  warranty  ceases  to  exist  if  the  buyer  does  not  follow  the  technical 
instructions included in official documents given by Olympia Electronics or if the buyer modifies the goods 
provided or has any repairs or re-setting done by a third party, unless Olympia Electronics has fully agreed 
to them in writing. Products that have been damaged can be returned to the premises of our company for 
repair or replacement, as long as the warranty period is valid.

NOTE!!

 The installer should fill in, on the specification label, the letter 

G

 if the luminaire is used as a 

safety sign.

European
manufacturers

72nd km. O.N.R. Thessaloniki-Katerini

P.C. 60300 P.O. Box 06 Εginio Pierias Greece

www.olympia-electronics.gr

info@olympia-electronics.gr

Non

maintained

NM

Thank you for your trust in our products  

Olympia Electronics - European manufacturer

25m

Maintained

Μ

Warranty

Manual Test

Lens Removal

2

2

1

3

1

1h/3h/8h

Duration

The light source contained in this luminaire shall only be replaced by the manufacturer, or 
his agent, or a similar qualified person.

NOTE!

! The light source is non-user replaceable.

2

2

1

1

4.  Replace the removed parts (previous steps 1 and 2).

3.  Remove the old battery and place a new one of the same type and characteristics.

2.  Follow step 2 of the installation instructions and remove the reflector.

1.  Follow step 1 of the installation instructions and remove the diffusor.

It can be done only by a competent person and after the mains interruption

.

Battery Replacement

OLY-1004/LT/WP

Olympia Electronics S.A.

10-12V DC

1h: 2W

3h: 1.1W

8h: 0.26W

2701205

50 °C max. across the board

Non reversible connection between main pcb and led module

LED Characteristics

MANUFACTURER
MODEL NUMBER

VOLTAGE RANGE

CONNECTIONS

NOMINAL POWER

TEMPERATURE (tc)

OLY-1004/LT/WP

220-240V AC / 50-60Hz

5.2W / 5.4VA

Technical Characteristics

OPERATION VOLTAGE

MAXIMUM POWER CONSUMPTION

4.8V/2 Ah

0.93

BATTERY (Li Ti O )

4

5

12

INSULATION BETWEEN SUPPLY & CONTROL TERMINALS

MINIMUM POWER FACTOR

WIRE CROSS SECTION

MAX OPEN CIRCUIT VOLTAGE

Irated

Prated

U-OUT

SUPPLY CURRENT

Basic insulation

1h: 2W

3h: 1.1W

8h: 0.26W

1h: 174mA

3h: 100mA

8h: 25mA

22V

22V

24.3mA

2

2

0.5mm  - 2.5mm

BATTERY PROTECTION

28 white LEDs

1 h, 3 h, 8 h

CHARGE TIME

MINIMUM DURATION
LIGHT SOURCE

16 hours

LED Charge, Lamp Fault LED, Battery Fault LED

EN 60598-1, EN 60598-2-22, ΕΝ 55015,
ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3

IP65

25m

VIEWING DISTANCE (as safety sign)

DEGREES OF COVER PROTECTION

PRODUCED IN ACCORDANCE WITH

OPERATION TEMPERATURE RANGE

o

-25 to 40  C

ABS/PC, PC

680gr.

270 x 147 x 48 mm

RELATIVE HUMIDITY

CONSTRUCTION MATERIAL

EXTERNAL DIMENSION (L x W x H)

WEIGHT
GUARANTEE

Up to 95% 

3 years

INDICATIONS

Deep discharge and overcharge protection / the control gear will recharge the battery normally after the test of 22.3

1h: 420-750mA

3h: 240-425mA

8h: 75-135mA

0-210mA

MIN MAX. DISCHARGE VOLTAGE
MIN MAX. DISCHARGE CURRENT
MIN MAX. CHARGE CURRENT
MAX CHARGE VOLTAGE

3.4-5.6V

5.6V

LIGHT SOURCE LUMINOUS FLUX (MAINS / EMERGENCY)

300lm / 350lm (1 h), 190lm (3 h), 50lm (8 h)

CONTROL GEAR MAX. TEMPERATURE:tc

o

54  C at U10

CONTROL GEAR WITH AUTOMATIC
TEST FUNCTION

350/190/50lm

Light output

o

-25-40

Reviews: