Enter the reset action of the output. See figure for details.
Auto
= Automatic action; This action allows the output to automatically reset off
at the trigger points per the Setpoint Action shown in Setpoint Output
Figures. The “on” output may be manually reset (off) immediately by the
front panel
RST
button or user input.The output remains off until the trigger
point is crossed again.
LAtCH
= Latch with immediate reset action; This action latches the output on at
the trigger point per the Setpoint Action shown in Setpoint Output Figures.
Latch means that the output can only be turned off by the front panel
RST
12
6.4 MODULE 4 - S
ETPOINT
O
UTPUT
P
ARAMETERS
(
4-SPt
)
PARAMETER MENU
The Setpoint Output Parameters are only active when an optional output
module is installed in the meter.
Enter the setpoint (output) to be programmed. The
n
in the following
parameters will reflect the chosen setpoint number. After the chosen setpoint
is completely programmed, the display will return to
SPSEL
. Repeat steps for
each setpoint to be programmed. Select
NO
to exit the module. The number of
setpoints available is setpoint output card dependent.
SETPOINT SELECT
SP-2
SP-1
NO
ª
«
NO
SPSEL
ª
«
2
HYS-n
HYSTERESIS VALUE
ª
«
0.0
tOF-n
ª
«
0.0
tON-n
OFF TIME DELAY
ON TIME DELAY
OUTPUT RESET ACTION
LAtCH
Auto
L-dLY
0.0
to
599.9
Sec
0.0
to
599.9
Sec
ª
«
Auto
rSt-n
1
to
59999
Enter desired hysteresis value. See Setpoint Output Figures for visual
explanation of how setpoint output actions (balanced and unbalanced) are
affected by the hysteresis. When the setpoint is a control output, usually
balanced hysteresis is used. For alarm applications, usually unbalanced
hysteresis is used. For unbalanced hysteresis modes, the hysteresis functions on
the low side for high acting setpoints and functions on the high side for low
acting setpoints.
Note: Hysteresis eliminates output chatter at the switch point, while time delay
can be used to prevent false triggering during process transient events.
Enter the time value in seconds that the output is delayed from turning on
after the trigger point is reached. A value of 0.0 allows the meter to update the
output status per the response time listed in the Specifications.
Enter the time value in seconds that the output is delayed from turning off
after the trigger point is reached. A value of 0.0 allows the meter to update the
output status per the response time listed in the Specifications.
Select
YES
to enable Setpoint 2 and access the setup parameters. If
NO
is
selected, the unit returns to
SPSEL
and setpoint 2 is disabled.
SETPOINT 2 ENABLE
NO
YES
ª
«
NO
Enb-2
Enter the action for the selected setpoint (output). See Setpoint Output
Figures for a visual detail of each action.
SETPOINT ACTION
ª
«
HI-Ub
Act-n
LO-Ub
HI-Ub
LO-bL
HI-bL
LO-Ub
=
HI-Ub
=
LO-bL
=
HI-bL
=
Low Acting, with unbalanced hysteresis
High Acting, with unbalanced hysteresis
Low Acting, with balanced hysteresis
High Acting, with balanced hysteresis
High Acting (Balanced Hys) =
HI-bL
Low Acting (Unbalanced Hys) =
LO-Ub
Low Acting (Balanced Hys) =
LO-bL
High Acting (Unbalanced Hys) =
HI-Ub
SETPOINT VALUE
Enter the desired setpoint value. The decimal point position for the setpoint
and hysteresis values follow the selection set in Module 1.
-19999
to
99999
ª
«
10000
SPt-n