Enter the reset action of the output. See figure for details.

Auto

= Automatic action; This action allows the output to automatically reset off

at the trigger points per the Setpoint Action shown in Setpoint Output
Figures. The “on” output may be manually reset (off) immediately by the
front panel 

RST

button or user input.The output remains off until the trigger

point is crossed again.

LAtCH

= Latch with immediate reset action; This action latches the output on at

the trigger point per the Setpoint Action shown in Setpoint Output Figures.
Latch means that the output can only be turned off by the front panel 

RST

12

6.4  MODULE 4 - S

ETPOINT

O

UTPUT

P

ARAMETERS

(

4-SPt

)

PARAMETER MENU

The Setpoint Output Parameters are only active when an optional output

module is installed in the meter. 

Enter the setpoint (output) to be programmed. The 

n

in the following

parameters will reflect the chosen setpoint number. After the chosen setpoint
is completely programmed, the display will return to 

SPSEL

. Repeat steps for

each setpoint to be programmed. Select 

NO

to exit the module. The number of

setpoints available is setpoint output card dependent.

SETPOINT SELECT

SP-2

SP-1

NO

ª

«

NO

SPSEL

ª

«

2

HYS-n

HYSTERESIS VALUE

ª

«

0.0

tOF-n

ª

«

0.0

tON-n

OFF TIME DELAY

ON TIME DELAY

OUTPUT RESET ACTION

LAtCH

Auto

L-dLY

0.0 

to

599.9

Sec

0.0 

to

599.9

Sec

ª

«

Auto

rSt-n

to

59999

Enter desired hysteresis value. See Setpoint Output Figures for visual

explanation of how setpoint output actions (balanced and unbalanced) are
affected by the hysteresis. When the setpoint is a control output, usually
balanced hysteresis is used. For alarm applications, usually unbalanced
hysteresis is used. For unbalanced hysteresis modes, the hysteresis functions on
the low side for high acting setpoints and functions on the high side for low
acting setpoints.

Note: Hysteresis eliminates output chatter at the switch point, while time delay

can be used to prevent false triggering during process transient events.

Enter the time value in seconds that the output is delayed from turning on

after the trigger point is reached. A value of 0.0 allows the meter to update the
output status per the response time listed in the Specifications.

Enter the time value in seconds that the output is delayed from turning off

after the trigger point is reached. A value of 0.0 allows the meter to update the
output status per the response time listed in the Specifications.

Select 

YES

to enable Setpoint 2 and access the setup parameters. If 

NO

is

selected, the unit returns to 

SPSEL

and setpoint 2 is disabled.

SETPOINT 2 ENABLE

NO

YES

ª

«

NO

Enb-2

Enter the action for the selected setpoint (output). See Setpoint Output
Figures for a visual detail of each action. 

SETPOINT ACTION

ª

«

HI-Ub

Act-n

LO-Ub

HI-Ub

LO-bL

HI-bL

LO-Ub

=

HI-Ub

=

LO-bL

=

HI-bL

=

Low Acting, with unbalanced hysteresis

High Acting, with unbalanced hysteresis

Low Acting, with balanced hysteresis

High Acting, with balanced hysteresis

High Acting (Balanced Hys) = 

HI-bL

Low Acting (Unbalanced Hys) = 

LO-Ub

Low Acting (Balanced Hys) = 

LO-bL

High Acting (Unbalanced Hys) = 

HI-Ub

SETPOINT VALUE

Enter the desired setpoint value. The decimal point position for the setpoint

and hysteresis values follow the selection set in Module 1.

-19999

to 

99999

ª

«

10000

SPt-n

Summary of Contents for DP63000A-I

Page 1: ...LP0694A omega com e mail info omega com For latest product manuals omegamanual info User sGuide Shop online at D DP P6 63 30 00 00 0A A I I D DP P6 63 30 00 00 0B B I I Digital P Panel M Meter...

Page 2: ...megashop cz Germany Austria Daimlerstrasse 26 D 75392 Deckenpfronn Germany TEL 49 0 7056 9398 0 FAX 49 0 7056 9398 29 Toll Free in Germany 0800 639 7678 e mail info omega de United Kingdom One Omega D...

Page 3: ...s Serial communications capability for RS232 or RS485 is added with a serial option module The DP63000 can be powered from an optional Power Supply Model Number DP6 MLPS1 that attaches directly to the...

Page 4: ...1 Recognized to U S and Canadian requirements under the Component Recognition Program of Underwriters Laboratories Inc UL Listed File E313547 UL508 CSA C22 2 No 14 M95 LISTED by Und Lab Inc to U S and...

Page 5: ...ver the rear of the unit to the back of the bezel The unit should be installed fully assembled Insert the unit into the panel cutout While holding the unit in place push the panel latch over the rear...

Page 6: ...commercial radio transmitter 4 Signal or Control cables within an enclosure should be routed as far as possible from contactors control relays transformers and other noisy components 5 In extremely h...

Page 7: ...tions must then be given to the potential of the user input common with respect to earth ground and the common of the plug in cards with respect to input common Before connecting signal wires the Inpu...

Page 8: ...he value and move to the next parameter PROGRAMMING MODE EXIT SEL BUTTON The Programming Mode is exited by pressing the SEL button with Pro NO displayed This will commit any stored parameter changes t...

Page 9: ...KEY style enter the first Input Value using the front panel buttons The Input Range selection sets the decimal location for the Input Value For Apply APLY style the meter shows the previously stored I...

Page 10: ...current calibration values to provide accurate current measurements Over time the electrical characteristics of the components inside the unit will slowly change with the result that the stored calib...

Page 11: ...n allows the SEL button to toggle through the enabled displays FRONT PANEL DISPLAY SELECT ENABLE SEL This selection allows the RST button to reset the selected value s FRONT PANEL RESET ENABLE RST The...

Page 12: ...en the setpoint is a control output usually balanced hysteresis is used For alarm applications usually unbalanced hysteresis is used For unbalanced hysteresis modes the hysteresis functions on the low...

Page 13: ...r input or RST button is activated momentary action the meter delays the event until the corresponding on output crosses the trigger off point Previously latched outputs are off if power up Display Va...

Page 14: ...PROGRAMMING QUICK OVERVIEW Press and hold SEL button to enter Programming Mode...

Page 15: ...therwise shall not exceed the purchase price of the component upon which liability is based In no event shall OMEGA be liable for consequential incidental or special damages CONDITIONS Equipment sold...

Page 16: ...rs Turbine Paddlewheel Systems Totalizers Batch Controllers pH CONDUCTIVITY pH Electrodes Testers Accessories Benchtop Laboratory Meters Controllers Calibrators Simulators Pumps Industrial pH Conducti...

Reviews: