PLATINUM
TM
Series User’s Guide
23
Reference Section: Initialization Mode (INIt)
Navigate to the installed thermocouple type. Supported types are as follows:
•
k
– Type K (factory default)
•
J
– Type J
•
t
– Type T
•
E
– Type E
•
N
– Type N
•
R
– Type R
•
S
– Type S
•
b
– Type B
•
C
– Type C
Select the indicated type.
4.1.2
Resistance Temperature Detector (RTD) Input Type (INIt >
INPt > Rtd)
Select
Rtd
as
the input type. Factory default configuration settings are three-wire, 100
Ω
,
using the European standard 385 curve. Note that the 392 and 3916 curves are only available
for 100
Ω
RTDs. If
Rtd
is selected and a specific configuration is not changed, the last saved
configuration will be used.
Navigate to the desired configuration parameter:
•
N.wIR
– Firmware selection of the number of wires for RTD connection (no jumpers
needed)
•
A.CRV
– Calibration curve covering both the international standard and the
resistance of the RTD
Select the option.
4.1.2.1
Number of RTD Wires (INIt > INPt > Rtd >
N.wIR)
Navigate to the desired setting. Settings include the following:
•
3 wI
– Three-wire RTD (factory default)
•
4 wI
– Four-wire RTD
•
2 wI
– Two-wire RTD
Select the indicated option.
4.1.2.2
Calibration Curve (INIt > INPt > Rtd > A.CRV)
Navigate to the desired setting. Settings include the following:
•
385.1
– European and most common standard at the conventional
resistance of 100
Ω
(factory default)
•
385.5
– European curve for 500
Ω
•
385.t
– European curve for 1000
Ω
•
392
– Old US standard (rarely used), at 100
Ω
only
•
3916
– Japanese standard, at 100
Ω
only