PLATINUM
TM
Series User’s Guide
55
Specifications
7.
Specifications
7.1
Inputs
Input Types
Thermocouple, RTD, Thermistor, Analog Voltage, Analog Current
Current Input
4 to 20 mA, 0 to 24 mA Scalable
Voltage Input
-100 to 100 mV, -1 to 1 V, -10 to 10 Vdc Scalable
Thermocouple Input
(ITS 90)
K, J, T, E, R, S, B, C, N
RTD Input (ITS 90)
100/500/1000 Ω Pt sensor, 2
-, 3- or 4-wire; 0.00385 (100
Ω
only), 0.00392
(100
Ω
only), or 0.003916 (100
Ω
only) curves
Configuration
Differential
Polarity
Bipolar
Accuracy
Refer to Table 7.1
Resolution
0.1°F/°C temperature; 10 µV process
Input Impedances
Process Voltage:
10 MΩ for +/
- 100 mV
Process Voltage:
1 MΩ for
other voltage ranges
Process Current:
5 Ω
Thermocouple: 10 K
Ω max
Temperature
Stability
•
RTD: 0.04°C/°C
•
TC at 25°C (77°F): 0.05°C/°C (cold junction compensation)
•
Process: 50 ppm/°C
A/D Conversion
24 bit Sigma Delta
Reading Rate
20 samples per second
Digital Filter
Programmable from 0.05 seconds (filter = 1) to 6.4 seconds (filter = 128)
CMRR
120 dB
Excitation
Firmware selectable (no jumpers to set) to 5, 10, 12, and 24 Vdc @ 25 mA
Setpoint Adjustment
-9999 to +9999 counts
Warm Up to Rated
Accuracy
30 min
7.2
Control
Action
Reverse (heat), direct (cool), or heat / cool
Autotune
Operator initiated from front panel
Adaptive Tune
User selectable; fuzzy logic continuous PID tuning optimization
Control Modes
On/off or the following time/amplitude Proportional Control Modes:
selectable Manual or Auto PID, Proportional, Proportional with Integral,
Proportional with Derivative
Cycle Time
0.1–199 seconds
Ramp and Soak
•
Up to 99 Saved Ramp and Soak programs
•
Up to 8 Ramp and 8 Soak segments with individually selectable
events per program
•
Definable End Actions include program linking
•
Ramp and Soak segment times: 00.00 to 99.59 (for HH:MM and
MM:SS)
Omega Engineering | www.omega.com