Approvals Information
8.
Approvals Information
This product conforms to the EMC directive 89/336/EEC amended by 93/68/EEC and with the
European Low-Voltage Directive 72/23/EEC.
Electrical Safety EN61010-1:2010
Safety requirements for electrical equipment for measurement, control, and laboratory
Double Insulation; Pollution Degree 2
Dielectric withstand Test per 1 min
•
Power to Input/Output:
2300 Vac (3250 Vdc)
•
Power to Input/Output
1500 Vac (2120 Vdc)
•
Power to Relays/SSR Output: 2300 Vac (3250 Vdc)
•
Ethernet to Inputs:
1500 Vac (2120 Vdc)
•
Isolated RS232 to Inputs:
500 Vac (720 Vdc)
•
Isolated Analog to Inputs:
500 Vac (720 Vdc)
•
Analog/Pulse to Inputs:
No Isolation
Measurement Category I
Category I includes measurements performed on circuits not directly connected to the Mains Supply
(power). Maximum Line-to-Neutral working voltage is 50Vac/dc. This unit should not be used in
Measurement Categories II, III, and IV.
Transients Overvoltage Surge (1.2 / 50uS pulse)
•
Input Power:
2500 V
•
Input Power
:
1500 V
•
Ethernet:
1500 V
•
Input/Output Signals:
500 V
EMC EN61326:1997 + and A1:1998 + A2:2001
Immunity and Emissions requirements for electrical equipment for measurement, control, and
laboratory are as follows:
•
EMC Emissions Table 4, Class A of EN61326
•
EMC Immunity
Table 1 of EN61326
UL File Number:
E209855
2
Low-voltage DC power option: Units configured for external low power DC voltage, 12
–
36Vdc.
3
Ibid.
4
I/O signal and control lines require shielded cables, and these cables must be located on conductive cable trays or
in conduits. The length of these cables should not exceed 30 meters.