2.1 - MOUNTING REQUIREMENTS
This instrument is intended for permanent installation, for indoor 
use only, in an electrical panel which encloses the rear housing, 
exposed terminals and wiring on the back.
Select a mounting location having the following characteristics:
1) It should be easily accessible;
2) There is minimum vibrations and no impact;
3) There are no corrosive gases;
4) There are no water or other fluid (i.e. condensation);
5) The ambient temperature is in accordance with the opera-

tive temperature (0 to 50 °C);

6) The relative humidity is in accordance with the instrument 

specifications (20% to 85 %).

The instrument can be mounted on panel with a maximum 
thickness of 15 mm. When the maximum front protection (IP65) 
is desired, the optional gasket must be mounted.
2.2 - GENERAL NOTES ABOUT INPUT WIRING
1) Do not run input wires together with power cables;
2) External components (like zener barriers, etc.) connected 

between sensor and input terminals may cause errors in 
measurement due to excessive and/or not balanced line 
resistance or possible leakage currents;

3) When a shielded cable is used, it should be connected at 

one point only;

4) Pay attention to the line resistance; a high line resistance 

may cause measurement errors.

2.3 - THERMOCOUPLE INPUT

Fig. 3 - Thermocouple input wiring
External resistance: 100

 max., max. error 0.5% of span.

Cold junction: automatic compensation from 0 to 50°C.
Cold junction accuracy: 0.1 °C/°C after a warm-up of 20 
minutes.
Input impedance: > 1 M

.

Calibration: according to EN 60584-1.
Note: Por TC wiring use proper compensating cable preferable 

shielded.

2.4 - PT100 INPUT

Fig. 4 - PT100 input wiring
Input circuit: current injection (135 µA).
Line resistance: not compensated.
Calibration: according to EN 60751/A2.
2.5 - PTC/NTC/PT1000 INPUT

Fig. 5 - PTC/NTC/PT1000 input wiring
Input circuit: current injection (25µA).
Line resistance: not compensated.

2.6 - OUTPUTS
Safety notes:
1) To avoid electrical shock, connect supply cables last.
2) For supply connections use 16 AWG or larger wires rated 

for at last 75°C.

3) Use copper conductors only.
4) SSR (Solid State Relay) Outputs are NOT isolated. A double 

or reinforced isolation between instrument output and power 
supply must be assured by the external solid state relay.

a) Output 1
Relay

Contact rating:  8 A /250 V cos

ϕ

 =1

3 A /250 V cos

ϕ

 =0.4

Operations: 

1 x 10

5

SSR

Logic level 0: 

Vout < 0.5 Vdc

Logic level 1:

12 V ±20% @ 1 mA
10 V ±20% @ 20 mA.

b) Output 2
Relay

Contact rating: 8 A /250 V cos

ϕ

 =1

3 A /250 V cos

ϕ

 =0.4

Operations:

1 x 10

5

SSR

Logic level 0: 

Vout < 0.5 Vdc

Logic level 1:

12 V ±20% @ 1 mA
10 V ±20% @ 20 mA.

2.7 - POWER SUPPLY

Power consumption: 5VA max.
Supply voltage:  100 V to 240 VAC/DC (+10%)

12 VDC (-15% to +10%)
24 VAC/DC (-15% to +10%)

Notes:
1) Before connecting the instrument to the electrical supply, 

make sure that line voltage is equal to the voltage shown 
on the identification label.

2) To avoid electrical shock, connect supply cables at the end 

of the wiring procedure.

3) For supply connections use 16 AWG or larger wires rated 

for at last 75°C.

4) Use copper conductors only.
5) Do not place signal cables parallelly or next to power 

cables or to noise sources.

6) The power supply input is NOT fuse protected.  Please, 

provide a T type 1A, 250 V fuse externally.

7) For DC power supply the polarity is a do not care condition.

3.1 - TECHNICAL SPECIFICATIONS
Case:
 Plastic, self-extinguishing degree: V-0 according to UL 94.
Front protection: IP 65 (when the optional panel gasket is 
mounted) for indoor locations according to EN 60070-1.
Rear terminals protection: IP 20 according to EN 60070-1.
Installation: Panel mounting.
Terminal block: 11screw terminals (screw M3, for cables from 
0.25 to 2.5 mm

2

 or from 22 AWG to 14 AWG).

Dimensions: 75 x 33 mm, depth 75.5 mm.
Cutout: 71 (-0 to +0.5 mm) x 29 (-0 to +0.5 mm).
Weight: 180 g approximately.
I

nsulation voltage: 2300 V rms according to EN 61010-1.

Display: one 3 digits red display h 12 mm.
Display updating time: 500 ms.
Sampling time: 130 ms.
Resolution: 20000 counts.
Total Accuracy: +0.5% E.S.V. +1 digit @ 25°C of room temp..
Electromagnetic compatbility and safety requirements:
Compliance:
directive EMC 2004/108/CE (EN 61326-1),

directive LV 2006/95/CE (EN 61010-1).

Installation category: II.
Pollution category: 2.
Temperature drift: It is part of the global accuracy.
Operating temperature: 0 to 50°C (32 to 122°F).
Storage temperature: -30 to +70°C (-22 to 158°F).
Humidity: 20% to 85% RH, non condensing.
3.2 - HOW TO ORDER
Model

CN38S = Controller with S-touch keyboard (capacitive keyboard)
Input:

T

= TC J or K

RTD

= PT100

TH

= PTC, NTC or PT1000

Output Out1:

R1

= SPDT 8A-AC1 relay

DC1

= VDC for SSR.

Output Out2:

R2

= SPDT 8A-AC1 relay

DC2

= VDC for SSR.

Power supply:

(none) = 100... 240 VAC

12V

= 12 VDC not isolated

24V

= 24 VAC/DC.

4.1 - INTRODUCTION
When the instrument is powered, it initially works according to 
the parameter values loaded in its memory.  The instruments 
behavior and its performance are governed by the value of the 
stored parameters.
At the first start up the instrument will use a "default" parameter 
set (factory parameter set); this set is a generic one (e.g. a TC J 
input is programmed).
We recommend that you modify the parameters to suit your ap-
plication (e.g. set the right input type, Control strategy and 
define an alarm, etc.).  To change these parameters you will 
need to enter the "Configuration procedure".
4.2 - INSTRUMENT BEHAVIOUR AT POWER UP
At power up the instrument can start in one of the following 
modes depending on its configuration:
Auto mode

The display will show the measured value;
The instrument is performing the standard loop control.

Stand by mode (St.bY)

The display will show alternately the measured value and 

the message <<St.bY>> or <<od>>;

The instrument does not perform any control (the control 

outputs are OFF);

The instrument is working as an indicator.

We define the above conditions as "Standard Display".

4.3 - FRONT PANEL DESCRIPTION

1 - Key 

Pressed for 5 s, it allows access to the parameters pro-

gramming mode.

In the programming mode, it is used for the change of the 

parameters and for the confirmation of the values.

Still in the programming mode, it can be used together with 

the 

 key to modify the level of access (operator level or 

configuration level) of the selected parameter.

During the normal functioning (not in programming phase), 

pressed together with the 

 key for 5 s, it allows to lock 

and unlock the keyboard.

During the normal functioning (not in programming phase), 

pressed together with the 

 key for 5 s, it allows the 

reset or the acknowledgement of the alarms.

2 - Key 

In the programming mode, it is used for to decrease the values

to be programmed and for the selection of the parameters.

During the normal functioning (not in programming phase), 

quickly pressed, it allows to visualize and to modify the 
value of the set point.

3 - Key 

In the programming mode, it is used to increase the values 

to be programmed and for the selection of the parameters.

Kept pressed for 3 s in the programming mode it can be 

used to exit from it and come back to the normal functioning.

Still in the programming mode, it can be used together with 

the P key, to modify the level of access (operator level or 
configuration level) of the selected parameter.

Pressed together with the 

 key for 5 s, it unlocks the 

keyboard, when previously locked.

During the normal functioning (not in programming phase), 

quickly pressed, it allows to visualize the output power.

4 - Key 

If programmed through par. "ub.F", pressed for 1 s in the 

normal functioning mode, it allows the switch on/off (Stand-
by) or to perform one of the possible functions (to start a 
cycle of Autotuning, etc.).

During the normal functioning (not in programming phase), 

pressed together with the 

 key for 5 s, it allows the reset 

or the aknowledgement of the alarms.

5 - LED Set

In the programming mode, it is used for indicating the level 

of programming of parameters.

If ub.F = Sb.o, when the instrument is in Stand-by mode, it 

remains the only lit LED.

In the normal functioning mode, it flashes when a key is 

pressed to indicates the pressure has happend on the key.

6 - LED Out1

It indicates the Out 1 condition ( compressor or tempera-

ture control device) activated (on), deactivated (off) or 
inhibited (flashing).

7 - LED Out2

It indicates the Out 2 condition.

8 - LED Tun

It indicates the Autotuning is in progress.

4.4 - HOW TO ENTER THE CONFIGURATION 

PARAMETERS

Press 

 key and keep it pressed.

Condition 1: the instrument will show "Ln" (lock ON).
The keyboard is locked.
Mantaining the pressure on the 

 key, also press the 

 

key. The LED Set begins to flash.
Keep the pressure on the two.
Keep the pressure on the two keys until the display shows "LF" 
(lock OFF).
Now release the keys. The keyboard is now unlocked.  
Note: If no button is pressed for a time longer than the time 

programmed with the Lo parameter, the key lock will be 
automatically enabled.

Condition 2: The instrument displays no message.  
In this situation we can have 2 different cases:
Case 1: The parameters protection (password) is not active.
Press 

 key and keep it pressed for around 5 seconds.

The display will show the code of the first configuration parameter.
With the 

 and 

 keys, select the parameter to be edited.

Case 2: The parameters protection (password) is active.  
Press 

 key and keep it pressed for more than 5 seconds. 

The display will show the code that identifies the first parameter 
that has been moved into the Operator level.
Press 

 key. The display will visualize 

"r.P".

Press P key again. The display will show "

0".

With the 

 and 

keys, program the password and confirm 

it pushing 

 key again.

Note: the factory default password is 0 (no password).
2.A) 
If the password is correct, the instrument will show the 

code that identifies the first configuration parameter.

2.B) If the password is not correct, the instrument will show "r.P" 

again.

a) Once entered into the configuration parameters, select the 

parameter to be modified using the 

 and 

keys.  

b) Press 

 key. The instrument will alternatively visualize 

the parameter's code and its value.  

c) Modify the value of the parameter using the 

 and 

 keys.

d) Press 

 key to memorize the new value. The display will 

return to visualize only the code of the selected parameter.

e) Working on 

 and 

keys, it is therefore possible to 

select another parameter and to modify it as described on 
points a, b, c, d.

Note: The instrument will only show the parameters applicable 

to its hardware options in accordance with the specific 
instrument configuration (i.e.setting AL1t [Alarm 1 type] 
equal to <<nonE>> [not used], all parameters related 
with the alarm 1 will be skipped).

To go out from the programming mode do not work on any key 
for around 30 s, or press

key for around 5 s.

4.5 - PARAMETERS PROTECTION THROUGH A PASSWORD
The instrument has a function that protects the parameters 
through a password, programmable through parameter "PP."
If you wish to have this protection, you have to set parameter 
"PP" to the number you'd like to be your password and then exit 
from parameters programming.
When the protection is active, to be able to have access to the 
parameters, press 

 key and keep it pressed for around 5 s. 

Afterwards, the display will visualize "r.P" , push the 

 key 

again and the display will visualize "0."  
Now, through the 

 and 

keys, set the number of your 

password and press 

 key.  

If the password is correct the display will visualize the code that 
identifies the first parameter and it will be possible to program it 
with the same procedure as described on the previous paragraph.
The protection through password is disabled setting par. "PP" = oF.
Note: If the password is forgotten, use password -18. This will 

allow you access to the protected parameters and it will 
be possible therefore to verify and also modify the 
parameter "PP."

4.6 - CUSTOMIZED PARAMETERS PROGRAMMING 

(levels of parameters programming)

The factory programming makes hides all the parameters 
behind the password with exception of the set point 1.
If you wish to modify some parameters, maintaining the 
protection on the others, after setting the Password through 
parameter "PP", it is necessary to follow this procedure:
a) Enter the programming through the Password.
b) Select the parameter to be programmable without password.
c.1) The LED Set is flashing.

the parameter is protected by the password.

c.2) The LED Set is lit but not flashing.

The parameter is not protected by the password.

To modify the level of access of the parameter (in other words: 
to have the parameter protected or not by the password) press 
the 

 key and keeping it pressed press the 

 key.

The LED Set will change its state, pointing out the new level of 
accessibility of the parameter (switched on = not protected; 
flashing = protected by password).
If the Password is enabled and some parameters have been set 
as "not protected", when entering the programming the 
instrument will first display all the parameters set as "not 
protected" and then,  "r.P" parameter. By entering the password 
here all other parameters can be viewed.
4.7 - FACTORY RESET

(default parameters loading procedure)

It is possible to restore the instruments factory configuration.
To load the factory default parameter settings, proceed as follows:

Enter in configuration mode (see 4.4 paragraph).  
If no password is programmed, set PP different from OFF.
Exit from configuration procedure.
Press the 

 button for more than 7 seconds. The display 

will show "rP".

Release the 

 button and push it again. The display will 

show "0".

By means of keys 

 and 

set the value 

-48.

Once the password has been confirmed by pressing the 

 

key, the display shows for approximatively 2 s "---", the 
instruments then runs through the start up procedure resetting 
all the parameters to the factory defaults.
4.8 - ON/STAND-BY FUNCTION
When supplied, the instrument can assume 2 different conditions:

- ON: means that the regulator activates the programmed 

control functions.

- STAND-BY: means that the regulator does not activate any 

control function and the control outputs are forced to zero 
(the display results switched on or off according to the pro-
gramming done on parameter ub.F).

The instrument starts in the same way it was before the switch off.
The condition of ON/STAND-BY can be selected through the 

 key when pressed for 1 s.

The passage from the STAND-BY to the ON condition, does 
not activate the Soft-start (or od) or the Autotuning and hides 
the alarms.
When the instrument is in STAND-BY mode with the display on 
the display alternates between the measure value and "St.b."
When the instrument is in STAND-BY with display off, the dis-
play is completely switched off except for the decimal point of 
the LSD (LED Set (5)).
When the instrument is in STAND-BY mode (both the visualiza-
tions) it is however possible to enter the parameters programming.
4.9 - ALL CONFIGURATION PARAMETERS
In the following pages we will describe all the parameters of the 
instrument.  However, the instrument will only show the 
parameters applicable to its hardware options in accordance 
with the specific instrument configuration (i.e.setting o2F 
[Alarm] equal to <<no>> [not used], all parameters related with 
the alarm will be skipped).
[1] SPL: Minimum Set Point value
Range:
 from -99.9 to SPH engineering units.
[2] SPH: Maximum Set Point value
Range:
 from SPL to 999 engineering units.
 [3] SP1: Set Point 
Range:
 from SPL to SPH engineering units.
[4] SP2: Second Set Point
Note: 
When 2 control outputs are programmed with ON/OFF 

action, the instrument uses SP1 to command OUT1 and 
SP2 (see following parameter) to command OUT2.

Available: When Out 2 has been programmed as control output.
Range: from SPL to SPH engineering units.
[5] AL : Alarm threshold
Available:
 when Out 2 has been programmed as alarm.
Range: -99.9 to 999 engineering units.

1. OUTLINE DIMENSIONS (mm)

2. CONNECTION DIAGRAM

Vr. 1 (ENG) - code.: ISTR-FCN38SENGOG1

 OMEGA Enineering, Inc.

One Omega Drive, P.O. Box 4047

Stamford, Connecticut 06907-0047

Phone: (800) 848-4286 or (203) 359-1660

Fax: (203) 359-7700

34

64

28

5.5

75

35

Type 1

panel gasket

Type 2

panel gasket

m

ax.

 2

9 m

m

max. 12 mm

Out2

Out1 Tun

AL

CN38S

POWER

SUPPLY

+

1

3

2

4

C

11

INPUTS

P T C / N T C

8

6

5

OUT1

NO

7

12

OUT2

R38

Relays: 8A-AC1

 

(6A-AC3)/250 VAC

Pt100/PT1000

tc

N C

N O

C

10

+

-

+

-

N C

SSR: 10 VDC/20 mA

11
12

+

-

11
12

+

-

RTD

11
12

+

-

PTC/NTC/PT1000

3. TECHNICAL CHARACTERISTICS

4. CONFIGURATION PROCEDURE

4

C

6

5

NO

N C

+

-

4

6

5

1

C

3

2

NO

N C

+

-

1

3

2

7
8

Power
supply

CN38S -

-

Input

Out1

-

Out2

-

Power supply

5

1

2

3

4

Out2

Out1 Tun

AL

CN38S

Normal Mode

Password request

Insert correct 

password

Increase
value

Decrease
value

Parameters 

(Program mode)

CN38S

Microprocessor Based 

Digital Electronic Controller 

INSTRUCTION

SHEET

M5309/1114